Service center of POWTRAN technology company
My future ,drive and control
Performing motor auto-turning to get the motor parameters
Automatically for
vector control application
.
8.How to perform motor auto-turning ?
1. Set F0.00=1 or 2 refer to whether you have PG card or not . (set corresponding
value in parameter b0.28 and b0.29 according to your encoder )
2. Typing motor parameters in parameter b.00-b0.05 according to your motor nameplate.
3. Disconnect load from motor for performing complete rotational auto-turning.
b0.00
motor type
0:General asynchronous motor
1:Asynchronous frequency conversion motor
2:permanent magnet synchronous motor
b0.01
rated power
0.1
~
1000.0KW
b0.02
rated voltage
1
~
2000V
b0.03
rated current
0.01A~655.35A (rated power <=55KW)
0.1A~6553.5A (rated power >55KW)
b0.04
rated frequency
0.01
~
F0.19 (maximum frequency )
b0.05
rated rotation speed
0
~
36000RPM
b0.27
motor auto-turning
selection
0:no operation
1,Asynchronous motor parameters still auto tunning.
2.Asynchronous motor parameters comprehensive
auto tunning.