Chapter 5 Function parameter
85
Ch
ap
ter 5
should be large, otherwise the poor inhibitory effect may cause overvoltage fault.
When the overvoltage stall gain is set to 0, the overvoltage stall function will be canceled.
F8.08
Output phase loss
protection selection
Prohibit
0
1
☆
Allow
1
Select whether the output phase loss protection is done or not.
F8.09
Power-on short circuit to ground
Invalid
0
1
☆
Valid
1
You can detect whether the motor is shorted to ground when the inverter is powered on.If
this function is active, the inverter's UVW terminal will output voltage after power-on for a
while.
F8.10
Number of automatic fault reset
0 to 32767
0
☆
When the inverter selects automatic fault reset, it is used to set the number of times of
automatic fault reset. If the set number of times is exceeded, the inverter remains a failed
state.When set F8.10 (number of automatic fault reset) ≥ 1, inverter will run automatically when
repower after instantaneous power-off. When fault self-recovery restart uptime over an hour
later, it will restore the original setting of automatic fault reset.
F8.11
Fault DO action selection during
automatic fault reset
OFF
0
0
☆
ON
1
If the inverter automatic fault reset function is set, F8.10 can be used to set whether DO
action is active or not during the automatic fault reset
F8.12
Automatic fault reset interval
0.1s to 100.0s
1.0s
☆
It is the waiting time from the inverter fault alarm to automatic fault reset.
F8.17
Fault protection
action selection
1
Units digit
Motor overload (Fault ID
Err.11)
00000
☆
Free stop
0
Stop at the selected mode
1
Continue to run
2
Tens digit
Input phase loss(Fault ID
Err.12)(Same as units digit)
Hundreds
digit
Output phase loss(Fault ID
Err.13)(Same as units digit)
Thousands
digit
External fault(Fault ID
Err.15)(Same as units digit)
Ten
thousands
digit
Communication
abnormal(Fault ID
Err.16)(Same as units digit)
F8.18
Fault protection
action selection
2
Units digit
Reserve
00000
☆
Tens digit
Function code fault(Fault ID
Err.21)
Free stop
0
Switch to V/F and then stop at the selected
mode
1
Hundreds
digit
Reserve
Thousand
s digit
Reserve
Ten
thousands
digit
Running time arrival(Fault ID
Err.26)( same as F8.17 units digit)
F8.19
Fault protection
action selection
3
Units
digit
Custom fault 1 (Fault ID
Err.27)( same as F8.17 units digit)
00000
☆
Tens digit
Custom fault 2 (Fault ID
Err.28)( same as F8.17 units digit)