Chapter 5 Function parameter
24
Ch
ap
ter 5
18
d0.18
High-speed pulse input
frequency
High-speed pulse input frequency display,
unit: 0.01Khz
0.01kHz
19
d0.19 Feedback speed(unit:0.1Hz)
PG feedback speed, to an accuracy of
0.1hz
0.1Hz
20
d0.20 Remaining run time
Remaining run time display, it is for
timing run control
0.1Min
21
d0.21 Linear speed
Display DI5 high-speed pulse sampling of
the line speed, according to the actual
sample pulse per minute and E0.07,
calculated the value of the line speed.
1m/Min
22
d0.22 Current power-on time
Total time of current inverter power-on
Min
23
d0.23 Current run time
Total time of current inverter run
0.1Min
24
d0.24
High-speed pulse input
frequency
High-speed pulse input frequency display,
unit: 1Hz
1Hz
25
d0.25 Communication set value
Frequency, torque or other command
values set by communication port
0.01%
26
d0.27 Master frequency display
Frequency set by F0.03 master frequency
setting source
0.01Hz
27
d0.28 Auxiliary frequency display
Frequency set by F0.04 auxiliary
frequency setting source
0.01Hz
28
d0.29 Command torque (%)
Observe the set command torque under
the torque control mode
0.1%
29
d0.35 Inverter status
Display run, stand by and other statuses
-
30
d0.36 Inverter type
1.G type (Constant torque load type)
2.F type (Fans/pumps load type)
-
31
d0.37
AI1 voltage before
correction
Input voltage value before AI1 linear
correction
0.01V
32
d0.39
Panel potentiometer voltage
before correction
Panel potentiometer oltage before linear
correction
0.01V
5-1-2.F0 Group - Basic function group
No.
Code
Parameter name
Setting range
Factory
setting
Chan
ge
33
F0.00 Motor control manner
0.Vector control W/O PG
1.Vector control W/ PG
2.V/F control
2
★
34
F0.01 Keyboard set frequency
0.00Hz to F0.19 (Maximum
frequency)
50.00Hz
☆
35
F0.02
Frequency command
resolution
1: 0.1Hz
2: 0.01Hz
2
★
36
F0.03 Frequency source
0 to 9
1
★