Chapter 5 Function parameter
104
Ch
ap
ter 5
static self learning. To set the parameters according to load conditions, and then press the RUN
button, the inverter will be parameter self learning. Parameters from the learning must be done
in keyboard mode, terminal and communications operation mode cannot be parameter self
learning.
0: No operation, namely parameters self-learning is prohibited.
1: Asynchronous motor parameters of static self learning. Prior to induction motor
parameters of static self learning, it is necessary to properly set b0.00 ~ b0.05 motor type and
motor nameplate parameters. Induction motor parameters of static self learning, inverter can
obtain b0.06 ~ b0.08 three parameters.
2: Asynchronous motor parameter self learning in an all-round way. Induction motor
parameter self learning process, the comprehensive frequency converter for static self learning
first, and then according to the acceleration time F0.13 to motor rated frequency 80%, after a
period of time, in accordance with the deceleration time F0.14 slow down and learn the end.
The motor type and motor nameplate parameters b0.00 to b0.05 should be set correctly before
the induction motor parameters are fully self-learning.
Induction motor parameter self learning comprehensively, inverter can obtain b0.06 ~
b0.10 five motor parameters, vector control current loop F5.12 ~ F5.15 PI parameters.
Note: The motor learning must be done in keyboard mode, terminal and communications
operation mode cannot be machine self-learning.
5-2-21.y0 group Function code management
Code
Parameter name
Setting range
Factory
setting
Change
limits
y0.00
Parameter initialization
no operation
0
0
★
restore default parameter values,
not including motor parameters
1
clear history
2
restore default parameter values,
including motor parameters
3
backup current user parameters
4
restore from backup user
parameters
501
1, restore the factory Settings, not including motor parameters
Set y0.00= 1, function of frequency converter parameters mostly recovery for the
manufacturer factory, but the motor parameter, frequency instruction decimal point (F0.02) and
fault recording information, total running time, the accumulative electric time, total power
consumption is not restored.
2, remove record information
Remove converter fault recording information, total running time, the cumulative time,
total power consumption.
3, parameter default values, including motor parameters.
4, backup the current user parameters
The parameters set the backup for the current user. The current backup function parameter
setting values all down. To facilitate customer recovery after parameter adjustment disorder.
501 backup, restore the user parameters.Restore the backup before user preferences
y0.01
User password
0
~
65535
0
☆
Y0.01 set any non zero number, password protection in effect. Next time when you enter
the menu, you must enter the password correctly, otherwise cannot view and modify the
function parameters, please keep in mind that set by the user's password.
Set y0.01 to 0, to clear set the user password, the password protection function is invalid.
y0.02
Function parameter
group display selection
Units digit d group display selection
11111
★
not displays
0
displays
1
Tens digit
E group display selection