Symptom

 

Possible cause

 

Remedy

 

Fault code is shown as 14 on 
LCD display and alarm is 

continuously sounding. 

The UPS shut down 

automatically because short 

circuit occurs on the UPS 

output. 

Check output wiring and  if 

connected devices are in 

short circuit status. 

Fault code is shown as 01, 02, 03,  A  UPS  internal  fault   has  Contact your dealer 

11, 12, 13 and 41 on LCD display  occurred.  There  are   two 
and alarm is continuously 

possible results: 

sounding. 

1. The load is still supplied, 

but directly from AC power 
via bypass. 
2.  The  load  is  no longer 

supplied by power. 

Battery backup time is shorter 
than nominal value. 

Batteries are not fully 
charged 

Charge the batteries for at 
least 5 hours and then 
check capacity. If the 

problem still persists, 
consult your dealer. 

Batteries defect 

Contact your dealer to 

replace the battery. 

Fault code is shown as 45 on LCD 
display. At the same time, alarm is 
continuously sounding. 

The charger does not have 
output and battery voltage 
is less than 10V/PC. 

Contact your dealer. 

 
 

 

5. Storage and Maintenance 

Operation  

The UPS system contains no user-serviceable parts. If the battery service life (3~5 years at 
25°C ambient temperature) has been exceeded, the batteries must be replaced. In this case, 
please contact your dealer.  

 
 

 
 

Storage  

Before storing, charge the UPS 5 hours. Store the UPS covered and upright in a cool, dry 
location. During storage, recharge the battery in accordance with the following table: 

Storage Temperature 

Recharge Frequency 

Charging Duration 

-25°C - 40°C 

Every 3 months 

1-2 hours 

40°C - 45°C 

Every 2 months 

1-2 hours 

 

 

 

 

Be sure to deliver the spent battery to a recycling facility or ship it to your 

dealer in the replacement battery packing material. 

 

 

 

Summary of Contents for VI TW 1.1K

Page 1: ...User Manual PowerWalker VI TW Series Uninterruptible Power Supply System Version 1 0...

Page 2: ...tion And Setup 4 2 1 Rear panel view 4 2 2 Operating principle 5 2 3 Setup the UPS 5 3 Operations 7 3 1 Button operation 7 3 2 LCD Panel 7 3 3 Audible Alarm 8 3 4 LCD display wordings index 9 3 5 UPS...

Page 3: ...Connect the UPS system only to an earthed shockproof outlet which must be easily accessible and close to the UPS system Please use only VDE tested CE marked or UL marked for 110 115 120 127 VAC models...

Page 4: ...ries Released electrolyte is harmful to the skin and eyes It may be toxic a Batteries may cause electric shock and have a high short circuit current Please take the precautionary measures specified be...

Page 5: ...tial environment this product may cause radio interference in which case the user many be required to take additional measures only for 220 230 240 VAC system Only for 110 115 120 127 VAC system NOTE...

Page 6: ...ace for future use 2 1 Rear panel view IEC Type 1 1K 1 5K 2K 3K NEMA Type 1 1K 1 5K 2K 1 Programmable outlets connect to non critical loads 2 Output receptacles connect to mission critical loads 3 AC...

Page 7: ...nd door Maintain minimum clearance of 100mm in the bottom of the UPS to avoid dust and high temperature 2 Maintain an ambient temperature range of 0 C to 45 C for UPS optimal operation For every 5 C a...

Page 8: ...sed a metal plate is connected to Pin 1 and Pin2 for UPS normal operation To activate EPO function remove two screws on EPO port and green connector will be removed Note The EPO function logic can be...

Page 9: ...election key Press this button to confirm selection in UPS setting mode SELECT Button Switch LCD message Press this button to change the LCD message for input voltage input frequency battery voltage b...

Page 10: ...ion Indicates the load level by 0 24 25 49 50 74 and 75 100 Indicates overload Programmable outlets information Indicates that programmable management outlets are working Mode operation information In...

Page 11: ...meters to set up the UPS Parameter 1 It s for program alternatives Refer to below table Parameter 2 is the setting options or values for each program 01 Output voltage setting Interface Setting Parame...

Page 12: ...ng Interface Setting Parameter 2 Set up the charger maximum current 1 2 4 6 8 setting the maximum charger current at 1 2 4 6 8 Ampere Default 8A Note This setting is only effective for super charger 0...

Page 13: ...Selection button for 3 seconds to enter Setting mode Step 3 Press the Up button ON MUTE to switch to 02 of program list Then press Enter button to enter value setting of parameter 2 Press the Up butto...

Page 14: ...regulation range but higher than low loss point the boost AVR will be activated Battery mode When the input voltage is beyond the acceptable range or power failure UPS will backup power from battery...

Page 15: ...every 2 seconds EPO enable Sounding every 2 seconds Over temperature Sounding every 2 seconds Charger failure Sounding every 2 seconds Battery fault Sounding every 2 seconds At this time UPS is off to...

Page 16: ...nal or internal battery is incorrectly connected Check if all batteries are connected well Fault code is shown as 27 on LCD display and alarm is continuously sounding Battery voltage is too high or th...

Page 17: ...ult your dealer Batteries defect Contact your dealer to replace the battery Fault code is shown as 45 on LCD display At the same time alarm is continuously sounding The charger does not have output an...

Page 18: ...103 110 5 10 1 minutes 110 150 5 10 10 sec 150 5 10 0 5 sec EFFICIENCY AC Mode 96 Buck Boost Mode 95 Battery Mode 88 up to 90 nominal battery voltage BATTERY Battery Type Number 12 V 7 Ahx2 12 V 9 Ahx...

Reviews: