4. Troubleshooting 

 

If the UPS system does not operate correctly, please solve the problem by using the 

table below. 

Symptom

 

Possible cause

 

Remedy

 

No indication and alarm even 
though the mains is normal. 

The AC input power is not 
connected well. 

Check if input power  cord 
firmly  connected  to  the 
mains. 

The AC input is  connected 
to the UPS output. 

Plug AC input power cord 
to AC input correctly. 

The icon

 and the warning 

EPO function is activated. 

Set  the  circuit  in   closed 

code

flashing on LCD display 

and alarm is sounding every 2 

position  to  disable  EPO 
function. 

seconds. 

The icon 

 and the 

warning code 

 flashing on 

LCD display and alarm is 
sounding every 2 seconds. 

Line and neutral 
conductors of UPS input 
are reversed. 

Rotate mains power socket 
by 180° and then  connect 
to UPS system. 

The icon 

 and the 

warning code 

 flashing on 

LCD display and alarm is 

sounding every 2 seconds. 

The external or internal 
battery is incorrectly 
connected. 

Check if all batteries  are 
connected well. 

Fault code is shown as 27 on 
LCD display and alarm is 
continuously sounding. 

Battery voltage is too  high 
or the charger is fault. 

Contact your dealer. 

Fault code is shown as 28 on 
LCD display and alarm is 

continuously sounding. 

Battery voltage is too  low 
or the charger is fault. 

Contact your dealer. 

The icon 

 and the 

warning code 

 flashing on 

LCD display and alarm is 
sounding every second. 

UPS is overload 

Remove excess loads  from 
UPS output. 

UPS is overloaded. Devices 
connected to the UPS are 

fed directly by the 
electrical network via the 
Bypass. 

Remove excess loads  from 
UPS output. 

After repetitive overloads, 
the UPS is locked in the 

Bypass mode. Connected 
devices are fed directly by 
the mains. 

Remove excess loads  from 
UPS output first. Then shut 

down the UPS and  restart 
it. 

Fault code is shown as 43 and the 
icon 

 is lighting on LCD display. 

Alarm is continuously sounding. 

The UPS shut down 

automatically because of 

overload at the UPS output. 

Remove excess loads  from 
UPS output and restart it. 

 

Summary of Contents for VI TW 1.1K

Page 1: ...User Manual PowerWalker VI TW Series Uninterruptible Power Supply System Version 1 0...

Page 2: ...tion And Setup 4 2 1 Rear panel view 4 2 2 Operating principle 5 2 3 Setup the UPS 5 3 Operations 7 3 1 Button operation 7 3 2 LCD Panel 7 3 3 Audible Alarm 8 3 4 LCD display wordings index 9 3 5 UPS...

Page 3: ...Connect the UPS system only to an earthed shockproof outlet which must be easily accessible and close to the UPS system Please use only VDE tested CE marked or UL marked for 110 115 120 127 VAC models...

Page 4: ...ries Released electrolyte is harmful to the skin and eyes It may be toxic a Batteries may cause electric shock and have a high short circuit current Please take the precautionary measures specified be...

Page 5: ...tial environment this product may cause radio interference in which case the user many be required to take additional measures only for 220 230 240 VAC system Only for 110 115 120 127 VAC system NOTE...

Page 6: ...ace for future use 2 1 Rear panel view IEC Type 1 1K 1 5K 2K 3K NEMA Type 1 1K 1 5K 2K 1 Programmable outlets connect to non critical loads 2 Output receptacles connect to mission critical loads 3 AC...

Page 7: ...nd door Maintain minimum clearance of 100mm in the bottom of the UPS to avoid dust and high temperature 2 Maintain an ambient temperature range of 0 C to 45 C for UPS optimal operation For every 5 C a...

Page 8: ...sed a metal plate is connected to Pin 1 and Pin2 for UPS normal operation To activate EPO function remove two screws on EPO port and green connector will be removed Note The EPO function logic can be...

Page 9: ...election key Press this button to confirm selection in UPS setting mode SELECT Button Switch LCD message Press this button to change the LCD message for input voltage input frequency battery voltage b...

Page 10: ...ion Indicates the load level by 0 24 25 49 50 74 and 75 100 Indicates overload Programmable outlets information Indicates that programmable management outlets are working Mode operation information In...

Page 11: ...meters to set up the UPS Parameter 1 It s for program alternatives Refer to below table Parameter 2 is the setting options or values for each program 01 Output voltage setting Interface Setting Parame...

Page 12: ...ng Interface Setting Parameter 2 Set up the charger maximum current 1 2 4 6 8 setting the maximum charger current at 1 2 4 6 8 Ampere Default 8A Note This setting is only effective for super charger 0...

Page 13: ...Selection button for 3 seconds to enter Setting mode Step 3 Press the Up button ON MUTE to switch to 02 of program list Then press Enter button to enter value setting of parameter 2 Press the Up butto...

Page 14: ...regulation range but higher than low loss point the boost AVR will be activated Battery mode When the input voltage is beyond the acceptable range or power failure UPS will backup power from battery...

Page 15: ...every 2 seconds EPO enable Sounding every 2 seconds Over temperature Sounding every 2 seconds Charger failure Sounding every 2 seconds Battery fault Sounding every 2 seconds At this time UPS is off to...

Page 16: ...nal or internal battery is incorrectly connected Check if all batteries are connected well Fault code is shown as 27 on LCD display and alarm is continuously sounding Battery voltage is too high or th...

Page 17: ...ult your dealer Batteries defect Contact your dealer to replace the battery Fault code is shown as 45 on LCD display At the same time alarm is continuously sounding The charger does not have output an...

Page 18: ...103 110 5 10 1 minutes 110 150 5 10 10 sec 150 5 10 0 5 sec EFFICIENCY AC Mode 96 Buck Boost Mode 95 Battery Mode 88 up to 90 nominal battery voltage BATTERY Battery Type Number 12 V 7 Ahx2 12 V 9 Ahx...

Reviews: