10
115:
presents output voltage is 115Vac
120:
presents output voltage is 120Vac (Default)
127:
presents output voltage is 127Vac
02: Programmable outlets enable/disable
Interface
Setting
Parameter 2:
Enable or disable programmable outlets.
ENA:
Programmable outlets enable
DIS:
Programmable outlets disable (Default)
03: Programmable outlets setting
Interface
Setting
Parameter 2:
Set up backup time limits for
programmable outlets.
0-999:
setting the backup time limits in minutes from 0-
999 for programmable outlets which connect to non-
critical devices on battery mode. (Default: 999)
04: Maximum charger current setting
Interface
Setting
Parameter 2:
Set up the charger maximum current.
1/2/4/6/8: setting the maximum charger current at
1/2/4/6/8 Ampere. (Default: 8A)
Note:
This setting is only effective for super charger.
06: Autonomy limitation setting
Interface
Setting
Parameter 2:
Set up backup time on battery mode for
general outlets.
0-999:
setting the backup time in minutes from 0-999 for
general outlets on battery mode.
DIS:
Disable the autonomy limitation and the backup time
will depend on battery capacity. (Default)
Note:
When setting as “0”, the backup time will be only
10 seconds.
07: Battery total AH setting
Interface
Setting
Parameter 2:
Set up the battery total AH of the UPS.
7-999:
setting the battery total capacity from 7-999 in AH.
Please set the correct battery total capacity if external
battery bank is connected.