3-6. Operating Mode Description 

Operating mode  Description 

LCD display 

ECO mode  

When the input voltage is within voltage 
regulated range, UPS will power the output 

directly from the mains. ECO is an 
abbreviation of Efficiency Corrective Optimizer. 
In this mode, when battery is fully charged, 
the fan will stop working for energy saving. 

 

Buck mode 
when AC is 
normal.  

When the input voltage is higher than the 
voltage regulation range but lower than high 
loss point, the buck AVR will be activated. 

 

Boost mode 
when AC is 
normal.  

When the input voltage is lower than the 
voltage regulation range but higher than low 
loss point, the boost AVR will be activated. 

 

Battery mode 

When the input voltage is beyond the 
acceptable range or power failure, UPS will 

backup power from battery and alarm is 
sounding every 10 seconds.  

 

Standby mode 

UPS is powered off and no output supply 
power, but still can charge batteries. 

 

Fault mode 

When a fault occurs, the ERROR icon and the 

fault code will be displayed. 

 

 

3-7. Faults Reference Code 

Fault event 

Fault code  Icon  Fault event 

Fault code 

Icon 

Bus start fail 

01 

Inverter output short 

14 

Bus over 

02 

Battery voltage too 

high 

27 

Bus under 

03 

Battery voltage too low 

28 

Inverter soft start fail 

11 

Over temperature 

41 

Inverter voltage high 

12 

Over load 

43 

 

Inverter voltage Low 

13 

Charger failure 

45 

 

 

 

Summary of Contents for VI TW 1.1K

Page 1: ...User Manual PowerWalker VI TW Series Uninterruptible Power Supply System Version 1 0...

Page 2: ...tion And Setup 4 2 1 Rear panel view 4 2 2 Operating principle 5 2 3 Setup the UPS 5 3 Operations 7 3 1 Button operation 7 3 2 LCD Panel 7 3 3 Audible Alarm 8 3 4 LCD display wordings index 9 3 5 UPS...

Page 3: ...Connect the UPS system only to an earthed shockproof outlet which must be easily accessible and close to the UPS system Please use only VDE tested CE marked or UL marked for 110 115 120 127 VAC models...

Page 4: ...ries Released electrolyte is harmful to the skin and eyes It may be toxic a Batteries may cause electric shock and have a high short circuit current Please take the precautionary measures specified be...

Page 5: ...tial environment this product may cause radio interference in which case the user many be required to take additional measures only for 220 230 240 VAC system Only for 110 115 120 127 VAC system NOTE...

Page 6: ...ace for future use 2 1 Rear panel view IEC Type 1 1K 1 5K 2K 3K NEMA Type 1 1K 1 5K 2K 1 Programmable outlets connect to non critical loads 2 Output receptacles connect to mission critical loads 3 AC...

Page 7: ...nd door Maintain minimum clearance of 100mm in the bottom of the UPS to avoid dust and high temperature 2 Maintain an ambient temperature range of 0 C to 45 C for UPS optimal operation For every 5 C a...

Page 8: ...sed a metal plate is connected to Pin 1 and Pin2 for UPS normal operation To activate EPO function remove two screws on EPO port and green connector will be removed Note The EPO function logic can be...

Page 9: ...election key Press this button to confirm selection in UPS setting mode SELECT Button Switch LCD message Press this button to change the LCD message for input voltage input frequency battery voltage b...

Page 10: ...ion Indicates the load level by 0 24 25 49 50 74 and 75 100 Indicates overload Programmable outlets information Indicates that programmable management outlets are working Mode operation information In...

Page 11: ...meters to set up the UPS Parameter 1 It s for program alternatives Refer to below table Parameter 2 is the setting options or values for each program 01 Output voltage setting Interface Setting Parame...

Page 12: ...ng Interface Setting Parameter 2 Set up the charger maximum current 1 2 4 6 8 setting the maximum charger current at 1 2 4 6 8 Ampere Default 8A Note This setting is only effective for super charger 0...

Page 13: ...Selection button for 3 seconds to enter Setting mode Step 3 Press the Up button ON MUTE to switch to 02 of program list Then press Enter button to enter value setting of parameter 2 Press the Up butto...

Page 14: ...regulation range but higher than low loss point the boost AVR will be activated Battery mode When the input voltage is beyond the acceptable range or power failure UPS will backup power from battery...

Page 15: ...every 2 seconds EPO enable Sounding every 2 seconds Over temperature Sounding every 2 seconds Charger failure Sounding every 2 seconds Battery fault Sounding every 2 seconds At this time UPS is off to...

Page 16: ...nal or internal battery is incorrectly connected Check if all batteries are connected well Fault code is shown as 27 on LCD display and alarm is continuously sounding Battery voltage is too high or th...

Page 17: ...ult your dealer Batteries defect Contact your dealer to replace the battery Fault code is shown as 45 on LCD display At the same time alarm is continuously sounding The charger does not have output an...

Page 18: ...103 110 5 10 1 minutes 110 150 5 10 10 sec 150 5 10 0 5 sec EFFICIENCY AC Mode 96 Buck Boost Mode 95 Battery Mode 88 up to 90 nominal battery voltage BATTERY Battery Type Number 12 V 7 Ahx2 12 V 9 Ahx...

Reviews: