30
Output:
Volt:
Freq:
CVCF:
230V
60Hz
Enable
1.
Volt:
208:
Presenting the rated output voltage with 208Vac
220:
Presenting the rated output voltage with 220Vac
230:
Presenting the rated output voltage with 230Vac
240:
Presenting the rated output voltage with 240Vac
The default value is
230Vac.
2.
Freq:
50Hz:
The output frequency is setting for 50Hz.
60Hz:
The output frequency is setting for 60Hz.
NOTE:
CVCF should be enabled first to modify this item.
If CVCF is disabled, output frequency will be decided according to the
latest normal utility frequency. If it is within 46Hz and 54Hz, the output
frequency will be 50.0Hz. If it is within 56Hz to 64Hz, the output
frequency will be 60.0Hz.
3.
CVCF:
Enable or disable CVCF (converter) mode.
Enable:
The output frequency will be fixed at 50Hz or 60Hz according
to setting of “Freq”. The input frequency could be from 46Hz to 64Hz.
Disable:
The output frequency will synchronize with the input
frequency within 46~54 Hz for 50Hz system or within 56~64 Hz for
60Hz system.
NOTE:
CVCF means Constant Voltage and Constant Frequency.
It
represents converter mode.
The default setting is
Disable.
4) SystemTime setting
(available or effective on all mode)
Interface
Description
SystemTime:
Date, time and calendar date can be modified via this interface. Input the
actual time, the unit will automatically adjust timer after “
” button is
pressed.
5) Others setting
Interface
Description
Others:
Hot Standby:
Audible Mute:
Disable
Disable
Language:
English
>>>
1. Hot standby
(only available or effective on bypass mode and
standby mode)
:
Enable:
Hot standby function is enabled. It means that the current UPS is
set to be host of hot standby system, and it will automatically restart
after AC recovery even without battery connected.
Disable:
Hot standby function is disabled. The UPS is running at normal
mode and can’t restart without battery.
The default setting is
Disable
.
2. Audible Mute
(available or effective for all mode)
:
Enable:
It is to mute the buzzer.
Disable:
It is to enable the buzzer when UPS have alarms or UPS is
working in bypass mode or battery mode.
The default setting is
Disable.
3. Language
(available or effective for all mode):
English:
All interface will show in English
4. Bat Mute
(available or effective on all mode)
:
Enable:
It is to mute the buzzer when UPS is in battery mode.