20
3-3-8. Turn off the UPS without utility power supply in Battery mode
1) When LCD is on home page, press the “OFF/ESC” button, LCD will show a prompt page of “Turn Off”;
Move the arrow to “Yes” by up or down button, then press “ON/ENTER”, the UPS will be turning off to
bypass mode with beeping once. You could also enter the “control menu” to select the instruction “Turn
Off” to turn off the UPS. Please refer to the section of “LCD operation”;
2) If there is no bypass input voltage, the UPS will cut off all power supply and there is no display shown on
the panel.
3-3-9. Operation of changing battery quantity (number)
The default battery (12V) quantity of this UPS system is 16 (for one series), but 17, 18, 19, 20 could also be
applied in this system. Changing the battery quantity setting, can setup from UPS LCD panel.
NOTE: This operation should be done by professional technicians, please contact the dealer for support
3-4. LCD Operation on UPS Module
3-4-1. LCD Structure
The entire LCD structure is demonstrated as diagram below.