6. Specifications
MODEL
VFI 10K CPH 3/3
VFI 10K CPH 3/1
PHASE
3 phase in / 3 phase out
3 phase in / 1 phase out
POWER CAPACITY
10kVA/ 10kW
TOTAL PARALLEL CAPACITY
100KVA/100KW (when all 10 modules are connected)
MAX. BATTERY SET NO.
10
INPUT
Nominal Voltage
3 x 360VAC/380VAC/400VAC/415VAC (3Ph+N+PE)
Voltage Range
190-520 VAC (3-phase) @ 50% load; 305-478 VAC (3-phase) @ 100% load
Frequency Range
40~70Hz
Power Factor
≧
0.99 @ 100% load
THDi
< 5% @ full linear load
OUTPUT
Output Voltage
360VAC/380VAC/400VAC/415VAC (3Ph+N)
208*/220/230/240VAC (L+N)
AC Voltage Regulation
± 1%
Synchronized Frequency Range
46~54Hz or 56~64Hz
Frequency Range (Batt. Mode)
50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
Current Crest Ratio
3:1 (max.)
Harmonic Distortion
≦
2 % THD (Linear Load);
≦
4 % THD (Non-linear Load)
Transfer Time from AC Mode
to Battery or Bypass Mode
zero
Waveform (Batt. Mode)
Pure Sinewave
EFFICIENCY
AC Mode
AC Mode: 94%; ECO Mode: 97%;
Battery Mode
93.5%
93%
BATTERY/CHARGER
Suitable Batteries
12VDC VRLA
Battery Numbers
Adjustable 16/17/18/19/20 pcs per half-string (negative and positive)
Nominal Voltage
+/-192V (for 32 pcs) to +/- 240V (for 40 pcs)
Nominal Voltage
+/-218V (for 32 pcs) to +/- 273V (for 40 pcs)
Charging Current
+/- 4A
INDICATORS
LCD/LED Display
UPS status, Load level, Battery level, Input / Output voltage, Discharge timer, and Fault
conditions
PHYSICAL
Dimension, D X W X H (mm)
678 X 418 X 129
Net Weight (kgs)
20.5
ENVIRONMENT
Operation Humidity
0-95 % RH @ 0- 40°C (non-condensing)
Noise Level
Less than 55dB @ 1 Meter
MANAGEMENT
Smart USB
Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8, Linux and MAC
Optional SNMP
Power management from SNMP manager and web browser
*Derate capacity to 90% of capacity when the output voltage is adjusted to 208VAC.
**Product specifications are subject to change without further notice.