25
Bat Test Mode M
IP1:230.0V/50.0Hz
IP2:230.0V/50.0Hz
IP3:230.0V/50.0Hz
OP1:230.0V/50.0Hz
OP2:230.0V/50.0Hz
OP3:230.0V/50.0Hz
Bat:192.0V/192.0V
Load: 0/ 0/ 0%
Backup Time: 10H
However, it could execute this test in Line/Converter mode and reminder will pop up in the screen. When “Yes” is
selected, the screen will return back to home page with “Battery Test Mode” displayed on top. If the test is
completed, the displayed status will change back to UPS current mode. There are four battery test types to select.
Refer to below table.
Table:
Battery Test Type
Setting Item
Sub Item
Explanation
Battery Test Type
Short Time
10-second test time.
Long Time
When testing time is longer than 1 minute, please select “Long
Time” and the duration is able to set up.
(1~99min)
10 min (Default)
Till to Bat Low
Test until the battery is low voltage.
b)
On Battery Test mode, it will display “Cancel Test” in control menu. When “Cancel Test” is selected, the
screen will change back to UPS current mode.
Control:
Cancel Test
Turn to Bps
SR Off
Charger Off
Turn Off
→
Cancel Test ?
Yes
No
→
Line Mode M
IP1:230.0V/50.0Hz
IP2:230.0V/50.0Hz
IP3:230.0V/50.0Hz
OP1:230.0V/50.0Hz
OP2:230.0V/50.0Hz
OP3:230.0V/50.0Hz
Bat:192.0V/192.0V
Load: 0/ 0/ 0%
3)
Turn to Bypass
If it is selected and confirmed, the UPS will transfer from Line mode to Bypass mode.
Control:
Bat Test
Turn to Bps
SR Off
Charger Off
Turn Off
→
Turn to Bps ?
Yes
No
→
Bypass Mode M
IP1:230.0V/50.0Hz
IP2:230.0V/50.0Hz
IP3:230.0V/50.0Hz
OP1:230.0V/50.0Hz
OP2:230.0V/50.0Hz
OP3:230.0V/50.0Hz
Bat:192.0V/192.0V
Load: 0/ 0/ 0%