29
1) Bypass setting
(only available or effective on bypass mode and standby mode)
Interface
Description
Bypass:
Status:
HighLoss V:
Open
Disable
240V
LowLoss V:
HighLoss F:
LowLoss F:
110V
54Hz
46Hz
1. Status
1.1 Open/Forbid:
Open:
Bypass allowed. When selected, UPS will run at Bypass mode
depending on bypass enabled/disabled setting.
Forbid:
Bypass not allowed. When selected, it’s not allowed for running
in Bypass mode under any situations.
The default setting is
Open.
1.2 Enable/Disable
This option appears only when Bypass status is set to “Open”.
Enable:
Bypass enabled. When selected, Bypass mode is activated.
Disable:
Bypass disabled. When selected, automatic bypass is
acceptable, but “manual bypass” is not available. “Manual bypass”
means users manually operate UPS to Bypass mode (for example, in AC
mode turning off the UPS to Bypass mode). Then, the UPS will go to
bypass mode but without output if it is turned off in AC mode.
The default setting is
Enable.
NOTE:
The following items are only available in bypass mode.
2. HighLoss V:
Set the acceptable high voltage for bypass. Setting range is
from (Rated Output Volt +11V) to 276V and the default value is 264V.
3. LowLoss V:
Set the acceptable low voltage for bypass. Setting range is
from 110V to (Rated Output Volt - 11V) and the default value is 110V.
4. HighLoss F:
Set the acceptable high frequency for bypass.
50 Hz system: Setting range is from 51Hz to 54 Hz.
60 Hz system: Setting range is from 61Hz to 64Hz.
The default value is 54.0Hz/64.0Hz.
5. LowLoss F
: Set the acceptable low frequency for bypass.
50 Hz system: Setting range is from 46.0Hz to 49.0Hz.
60 Hz system: Setting range is from 56.0Hz to 59.0Hz.
The default value is 46Hz/56Hz.
2) ECO setting
(only available or effective on bypass mode, standby mode, Line mode and ECO mode)
Interface
Description
ECO:
Status:
HighLoss V:
Disable
240V
LowLoss V:
HighLoss F:
LowLoss F:
218V
52Hz
48Hz
1.
Status
Enable:
ECO function enabled
Disable:
ECO function disabled
If ECO function is disabled, voltage range and frequency range for
ECO mode still can be set, but it is meaningless unless the ECO
function is enabled. The default setting is
Disable.
2.
HighLoss V:
High voltage point in ECO mode. The setting range is from
(Rated Output Volt +11V) to (Rated Output Volt +24V) and the default
setting is (Rated Output Volt +11V).
3.
LowLoss V:
Low voltage point in ECO mode. The setting range is from
(Rated Output Volt -24V) to (Rated Output Volt-11V) and the default
setting is (Rated Output Volt -11V).
4.
HighLoss F:
Set High frequency point for ECO mode.
50 Hz system: Setting range is from 52Hz to 54Hz.
60 Hz system: Setting range is from 62Hz to 64Hz.
The default value is 52Hz/62Hz.
5.
LowLoss F:
Set Low frequency point for ECO mode.
50 Hz system: Setting range is from 46Hz to 48Hz.
60 Hz system: Setting range is from 56Hz to 58Hz.
The default value is 48Hz/58Hz.