Figure 3-16 Setup-Battery Screen
Table 3-9: Setup-Battery Setting List
Setting Item
Sub Item
Explanation
Nominal Battery
Voltage
--
Set battery nominal voltage
16x12V (Default)
18x12V
20x12V
MUST be set after UPS installation
Battery Capacity
in Ah
--
Set battery capacity. (up to 999)
9Ah (Default)
MUST be set after UPS installation or Battery capacity is
changed.
Maximum
Charging Current --
Set battery maximum charging current (1~24A 100KVA/1~32A
120KVA/1~40A 160KVA/1~48A 200KVA)
2A (Default)
MUST be set after UPS installation or Battery capacity is
changed.
Battery Low/
Shutdown Setting
Low Voltage
Set battery low voltage (10.5~11.5V)x(battery Number)
11V x Battery Number (Default)
Low Capacity
Set battery low capacity (20~50%)
20% (Default)
Shutdown Voltage
Set battery voltage point for system shutdown in battery mode
(10.0~11V) x (battery Number)
10V x Battery Number (Default)
Battery Test
Periodic Battery Test
Set periodic battery test disable or enable
Disable (Default)
Enable
Battery Test Interval
Set battery test interval (7~99 Days)
30 Days (Default)
Stop by Time
Set testing time for battery test (10~1000sec)
10 sec (Default)
Stop by Battery
Voltage
Set stop battery voltage in battery test (11~12V) x (battery
Number)
11V x Battery Number (Default)
Stop by Battery
Capacity
Set battery capacity to stop battery-testing. (20~50%)
20% (Default)
Battery Age Alert Battery Age Alert
(Months)
Set battery age for replacement. (Disable,12~60Months)
Disable (Default)
If this feature is enabled and the battery has been installed over
this period, there is a warning “Battery Age Alert” to indicate it.