Fault! EEPROM Fault
EEPROM operation error
Contact service personnel.
Fault! Parallel Cable Loosen
Fault
As stated.
Check if the parallel cable is loose
and contact service personnel.
Fault! DSP MCU Stop
Communicate
As stated.
Contact service personnel.
Fault! Bypass Temperature
Fault
As stated
Check if the ambient temperature is
over specification.
Or contact service personnel.
Fault! Bypass SCR Fault
As stated.
Contact service personnel.
Warning! EPO Active
Check the EPO connector
Check if the connector is loose
when EPO acts abnormally.
Warning! Over Load Fail
The load devices are demanding more
power than the UPS can supply. Line
mode will transfer to Bypass mode.
Reduce some load and check output
Load-Capacity and specification
Warning! Communicate CAN
Fail
CAN communication error
Contact service personnel.
Warning! Over Load
In Line mode, the load devices are
demanding more power than the UPS
can supply.
Reduce some load and check output
Load-Capacity and specification
Warning! Battery Open
Battery is not connected.
1.
Check battery breaker.
2.
Check if the battery connection
is well connected.
3.
Check the setting of Nominal
Battery voltage.
4.
Contact service personnel if
necessary.
Warning! Battery voltage
High
Battery voltage is too High
Check the setting of Nominal
Battery voltage and contact service
personnel.
Warning! Turn On Abnormal As stated.
Check if the input voltage or
frequency is out of range.
Warning! Charge Fail
As stated.
Contact service personnel.
Warning! EEPROM Fail
EEPROM operation error
Contact service personnel.
Warning! Fan Lock
As stated.
Check if the fan is blocked or
contact service personnel.
Warning! Line Phase Error
As stated.
Check if the Mains phase sequence
is correct and contact service
personnel.
Warning! Bypass Phase
Error
As stated.
Check if the Bypass phase sequence
is correct and contact service
personnel.
Warning! N Loss
Neutral loss
Check if the Neutral connection is
well and contact service personnel.
Warning! Internal Initial Fail As stated.
Contact service personnel.
Warning! Comm. Syn. Signal
Fail
Communicate Synchronization Signal
Fail
Contact service personnel.
Warning! Comm. TRIG0 Fail Communicate Trigger signal fault
Contact service personnel.
Warning! Power Stage Loss As stated.
Check if the number of power
stage/module installed in the
system is correct.
Warning! Parallel Sys
Parallel System Configure error
Contact service personnel.