27
Bypass Frequency Range
Set bypass Frequency range:
Upper/ Lower limit
+/- 1Hz
+/- 2Hz
+/- 4Hz (Default)
Converter
Mode
--
Set converter mode
Disable (Default)
Enable
ECO Mode
--
Set ECO mode
Disable (Default)
Enable
Bypass Mode --
Set bypass mode
Disable (Default)
Enable
MUST be reviewed after UPS installation.
If you need the Bypass power when UPS is OFF, please enable it.
Auto-Restart --
Set auto-restart
Disable
Enable (Default)
After “Enable” is set, once UPS shutdown occurs due to low
battery and then utility restores, the UPS will return to line mode.
Cold Start
--
Set cold start
Disable
Enable (Default)
After “Enable” is set, the UPS can be turned on without
connecting to utility by pressing Battery Start Button. Refer to
cold start operation for the details. (
Refer to Section 6-2. Cold
Startup.
)
Battery Mode
Delay Time
--
Set system shutdown delay time in battery mode (0~9990sec).
0: Disable (Default)
Not 0: Enable
When this feature is enabled, UPS will shut off output after UPS
operates in Battery mode for certain seconds.
Shutdown/
Restore
System Shutdown Time
Set system shutdown time (0.2~99min)
0.2 min (Default)
This delay time will start counting when the CONTROL-Shutdown
Restore command is executed.
System Restore Time
Set system restore time (0~9999min)
1 min (Default)
This delay time will start counting after shutdown time is elapsed
when the CONTROL-Shutdown Restore command is executed.
Charger Test --
Set charger test
Disable (Default)
Enable
3-2-5-3. Setup-Battery Screen
The Setup-Battery Screen and Setting options are shown in Figure 3-16 and Table 3-9. Battery Setting can
only be set when UPS is operated in STANDBY mode.