51
Step 4
Single input model:
Switch OFF the Input1 Breaker (Q1) as
shown below.
Dual input model :
Switch OFF the Input1 Breaker (Q1) and
Input2 Breaker (Q2) as shown below.
Single input model:
Switch OFF the Input1 Breaker (Q1) as
shown below.
Dual input model :
Switch OFF the Input1 Breaker (Q1), Input2
Breaker (Q2) and Output Breaker (Q3) as
shown below.
Step 5
It is possible to change the power stage/module now.
6-3-2. Transfer to UPS Protection
Step 1
Make sure the maintenance is complete. All power stages/modules have been installed
well.
Step 2
Single input model:
Switch ON the Input1 Breaker (Q1) as
shown below.
Single input model:
Switch ON the Input1 Breaker (Q1) as
shown below.