26
3-2-5-2. Setup-System Screen
The Setup-System Screen and setting options are shown in Figure 3-14 and Table 3-8. System Setting can
only be access when UPS is operated in certain mode. Please refer to Table 3-5 for the details. If an option is
not available under specific mode, a warning screen will appear such as in Figure 3-15.
Figure 3-14 Setup-System Screen
Figure 3-15 Warning Screen
Table 3-8: Setup-System Setting List
Setting Item Sub Item
Explanation
Output
Voltage
--
Set output voltage
220Vac (Default)
230Vac
240Vac
MUST be reviewed after UPS installation
BYPASS
SETTING
Bypass Voltage Range
Set bypass voltage range:
Upper limit
+10%
+15% (Default)
+20%
Lower limit
-10%
-20% (Default)
-30%