35
Fig. 5-16 Measurement menu tree
5.4.5 The Control Menu
By pressing
on the menu of “Control”, the display would enter the
next control menu tree.
1)
Start Battery Test: is one command to control the UPS to do the
battery test.
2)
Clear EPO status: once EPO status is enabled, the UPS output
would be cut off. To recover to normal status, first EPO connector
should be opened, and enter this menu to clear EPO status, then
UPS would stop alarm and recover to Bypass model. And UPS
needs be turned on by manual operation.
3)
Reset Fault status: when fault occurs, UPS would keep in Fault
mode and alarm. To recover to normal status, enter this menu to
reset error status, then UPS would stop alarm and recover to
Bypass mode. And the reason of fault should be checked and
deleted before UPS is turned on again by manual operation.