12
3) Operating Environment
Temperature
Humidity
Altitude
Storage temperature
0
°
C-45
°
C
<95%
<1000m
-15
°
C-50
°
C
Note: if the UPS is installed or used in a place where the altitude is
above than 1000m, the output power must be derated in use, please
refer to the following:
Altitude (M) 1000 1500 2000 2500 3000 3500 4000 4500 5000
Maximum
Power
100% 95% 91% 86% 82% 78% 74% 70% 67%
Output
Voltage
Regulation
Power
Factor
Frequency
tolerance.
Distortion Overload capacity Current
crest ratio
±
1%
0.9 lag
Synchronized
50/60Hz
±
10%
in Line mode
(AC mode)
±
0.1% of
normal
frequency in
Battery mode
THD<2%
Full load
(Linear
Load)/
<5% for
reference
non-linear
load
100%-110% load
transfers to Bypass
mode after 5
minutes
110%-130% load
transfers to Bypass
mode after 1
minutes
130%-150% load
transfers to Bypass
mode after 10
second
>150% load
transfers to Bypass
mode after 2 second
3:1