Med Touch Series LCD Alarm Systems
Powerex
•
150 Production Drive
•
Harrison, OH 45030
•
USA
P 1.888.769.7979
•
F 513.367.3125
•
www.powerexinc.com
IN597400AV
•
08/2016
Page 38 of 56
From the Main Page of the RTA website, click on Modbus RTU Master. An example Modmap of what is displayed is shown below. The
Read Scan Lines are generated automatically by the Ethernet/Rabbit board and will match the configuration of the alarm panel. Individual
informational items may be selected to communicated to the BACnet module for use on the building automation system.
BACnet/IP Server Settings
1. Click on the BACnet/ IP Server button. This will put the gateway into configuration mode so you can edit the BACnet settings.
2. Enter the Device instance that the 460MMBS will have on the BACnet/ IP Network. Note that this must be unique amongst all BACnet
devices on the network.
3. In the Name field enter a unique name for the device.
4. The Description and Location fields are optional. Filling in this information is recommended to identify the device on a network.
5. Beneath the Read Groups, verify the number of Analog Input (AI), Analog Outlet (AO), Binary Input (BI) and Binary Output (BO) objects
that you will be exposing to the BACnet/ IP Client.
6. Click Save Parameters.
7. To save changes and force the gateway back to running mode, click on the Reboot Now button and after 5 seconds hit the Refresh button.
You should see the gateway appear in the Mode: Running.