11-4
PODS 16.48-16000 1940 HEX
Document number: 038222.fm
Revision: B
Product description PBDU 4U/23”
11.5 Installation
This section details how to connect the -48 V DC supply to the DC load.
Check that all the MCB breakers and the AC mains supply are in the OFF position.
Unscrew the cabinet's four top fixing screws and slide top-cover forward before lifting it up. Enter each load
cable in to the cabinet trough the inlet at the back of the cabinet.
Connect the negative (-) load DC supply cable to the appropriate negative DC distribution MCB by inserting
the stripped cable in the opening on top of the MCB and tightening the screw. Make sure the cable is the
correct rating (i.e. thick enough) for the selected MCB.
Connect the positive (+) load DC supply cable directly to the positive busbar by inserting the stripped cable
to the hole on top of the screw connector so that the cable is behind the busbar, and then tightening the
screw. Start connecting the loads to the busbar from the first connector on the left. Make sure, the cable is
the correct rating (i.e. thick enough) for the load.
Check, that all the cables are secured tightly to the connectors. Use
Torque Table
in the Maintenance and
troubleshooting chapter for the correct torque.
11.6 Commissioning PBDU
1. Switch on all MCB's in the distribution units.
2. Turn off one of the breakers and verify breaker alarm at controller.
3. Verify disappearing of alarm when turning the breaker on again.
4. Repeat the two above-mentioned steps for one MCB in each distribution module.
11.7 Maintenance
The distribution does not need any special maintenance except for ordinary cleaning.
Summary of Contents for PODS 16.48-16000 1940 HEX
Page 4: ...1 2 PODS 16 48 16000 1940 HEX Document number titlepage fm Revision B...
Page 10: ...2 6 PODS 16 48 16000 1940 HEX Document number 039158TOC fm Revision B...
Page 23: ...Safety 5 1 Document number 028580 fm Revision A Safety 5 Safety...
Page 40: ...6 14 PODS 16 48 16000 1940 HEX Document number 039160 fm Revision A Installation guide...
Page 41: ...Commissioning 7 1 Document number 036285 fm Revision A Commissioning 7 Commissioning...
Page 92: ...A 10 PODS 16 48 16000 1940 HEX Document number Appendix A fm Revision B Drawings...
Page 94: ...B 2 PODS 16 48 16000 1940 HEX Document number 039418 fm Revision B Configuration c 000313...
Page 95: ...Configuration c 000313 B 3 Document number 039418 fm Revision B Configuration c 000313...
Page 96: ...B 4 PODS 16 48 16000 1940 HEX Document number 039418 fm Revision B Configuration c 000313...