POWER ELECTRONICS
PROFIPOWER
INSTALLATION AND CONNECTION
19
3.2.3.2.
Variable Speed Drives of SD450 Series
Use C+ terminal to connect the RS485 high signal and C- terminal to
connect the RS485 low signal.
Ground will be connected to the CM terminal. All of these terminals
are located in the connector of the figure.
SD45DTC0012AE
Figure 3.6 TER2 connector of control board
RS485 communication data:
Transmission form:
Bus method, Multi drop Link System.
Applicable drives:
SD450.
Connectable drives:
Maximum 31.
Transmission distance:
Below 1200m maximum (700m recommended).
Recommended cable:
0.75mm² (18AWG), shield type twisted-pare.
Installation:
C+, C- and CM terminals.
Power supply:
Power supply insulated from the drive power supply.