Page 33 of 52
PG2021_SWC-V-ECM_02
Holding Register table:
Description
Address
Type*
Remark
Mode setting
300000
R/W
Cooling mode = 01(H)
Humidify mode = 02(H)
Fan mode = 04(H)
Heating mode = 08(H)
Auto mode = 10(H)
Fan speed setting
300001
R/W
Low speed = 04(H)
Medium speed = 02(H)
High speed = 01(H)
Auto fan speed = 07(H)
Louver swing setting
300002
R/W
Position 1=01(H)
Position2=02(H)
Position3=03(H)
Position4=04(H)
Auto=0F(H)
Stop=00(H)
Setting temperature
300003
R/W
16~30 (actual*10 format)
Address setting
300004
R/W
1~255
Reset
300005
W
=0x33 reset error
Week
300006
W
Hour
300007
W
Minute
300008
W
Second
300009
W
Hours in Timer on
300010
R/W
Timer ON
Minute in Timer on
300011
R/W
Timer ON
Hours in Timer off
300012
R/W
Timer OFF
Minute in Timer off
300013
R/W
Timer OFF
Icon of Timer ON or OFF
300014
R/W
BIT0 = Icon of Timer ON
BIT1 = Icon of Timer OFF
1 = enable
0 = disable
Minimum output DA1
300015
R/W
Default 25% (2.5VDC)
Minimum output DA2
300016
R/W
Default 25% (2.5VDC)
Pre-heat temperature setting
300017
R/W
25~35, default: 30
Reserved-
300018
R/W
Super low speed rpm
300019
R/W
Low speed rpm
300020
R/W
Medium speed rpm
300021
R/W
High speed rpm
300022
R/W
Signal output setting
300023
R/W
1~10VDC (used to test, 0 = disable)
Temperature sampling time
300024
R/W
2~100, default: 5S
Factor of auto fan speed
300025
R/W
2~150, default: 20
Factor of modulating valve
300026
R/W
2~250, default: 150
Ti1 and Ti2 Cooling difference
setting
300027
R/W
3~15, default: 5
Ti1 and Ti2 Heating difference
setting
300028
R/W
3~15 default: 5
Controller Hardware type setting
300029
R/W
0=air cleaner (S5)
1=FCU (S1/S2/S3, SWC-S)
2=AHU (S6) or (AHU+W5)
3=AHU+AQI (S5+S6 )
4=Zone controller(S7) Setting: 1
Degree unit setting
300030
R/W
0=degree C
1=degree F
Temperature display setting
300031
R/W
0=Room temperature display on LED
1=Setting temperature display on LED