Before Installation
Select the location for the high- wall unit with the following considerations:
1.
The air inlet and outlet area should be clear without obstructions. The air should flow freely.
2.
The high wall unit should be mounted on solid wall.
3.
The location should allow easy access to connect water pipes easily achieve drainage.
4.
Ensure the clearance around the fan coil unit conforms to the following drawing.
*
Required clearance for maintenance and servicing is as shown above.
**
All dimensions shown in mm.
5.
The unit should be installed higher than eye level.
6.
Avoid installing the unit with direct sunlight.
7.
The signal receiver on the unit must be kept away from any high frequency emission source.
8.
Keep the unit away from fluorescent lamps, which may affect the control system.
9.
Avoid electromagnetic control system interference, ensure control wires are installed separately from 110-240 VAC power
supply wires.
10.
Use shielded sensor cables in where electromagnetic waves present.
11.
Install a noise filter if the power supply creates any disruptive noises.