Electric Heater Safety Switch
Low Temperature Protection of Indoor Coil in Winter
This is frost protection for when the unit is off to prevent water in the coil and room from freezing.
If 2pipe unit is in Standby Mode
If Tr
≦
2 ºC for 2 minutes
MTV1 is turned ON.
AUX2 is closed.
DA2 is 5 VDC.
If Ti1 <5 ºC for 2 minutes EH (if present) is switched on.
Indoor fan is turned on at low speed.
If Tr
≧
5ºC for 2 minutes
MTV2 is off.
AUX2 is open.
DA2 is set to 0 VDC.
Electric Heater is turned off.
Indoor fan is switched off.
If 4-pipe unit is in Standby Mode
If Tr
≦
2 ºC for 2 minutes
MTV2is turned ON.
AUX2 is closed.
DA3 is 5VDC. If unit with 6-way valve, DA2 is 8 VDC.
If Ti1 < 5 ºC for 2 minutes EH (if present) is switched on.
Indoor fan is turned on at low speed.
If Tr
≧
5ºC for 2 minutes
MTV2 is OFF.
AUX2 is open.
DA3 is set to 0. If unit with 6-way valve, DA2 is 5 VDC.
Electric Heater is turned off.
Indoor fan is switched off.