Page 46 of 52
PG2021_SWC-V-ECM_02
Long press
for 5 seconds then short press it twice to set Timer ON.
Press
to set day of week from Monday to Sunday.
Press
or
to change Timer ON time.
Press
to turn Timer ON on or off and S8 appears or disappears.
Long press
for 5 seconds then short press it
3 times to set Timer OFF time.
Press
to set day of week from Monday to Sunday.
Press
or
to change Timer OFF time.
Press
to turn Timer OFF on or off and S10 appears or disappears.
Long press
for 5 seconds then short press it 4 times to
set group control and U31 appears.
The function is reserved.
Long press
for 5 seconds then short press it 5 times
to set unit address and U32 appears.
Press
or
to change unit address.
*** For
MODBUS
user only
Long press
for 5 seconds then short press it 6 times
to set unit parameters. Press
to change
the parameter type. Press
or
to change parameter setting value.
S31/S32 displays “U001”, which is used to set unit type.
0=iAIR ……………
Mode: Ventilation T, RH, CO2, PM2.5 are displayed.
1=iFCU ……………
Mode: S12, S13, S14, S15, S16, S21 or S20 is displayed.
2=iAHU ……………
Mode: S12, S13, S14, S15, S16, S21 or S20 is displayed.
3=iAHU with air cleaner …………… Mode: S12, S13, S14, S15, S16, T, RH, CO2, PM2.5 are displayed.
S31/S32 displays “U002”, which is used to set unit of temperature degree.
0=Celsius degree.
1=Fahrenheit degree.
S31/S32 displays “U003”, which is used to select display temperature on LCD.
1=Setting temperature.
0=Room temperature.
S31/S32 displays “U004”, which is used to set setting temperature range.
0=Setting temperature is from 16~30°C.
1=Cooling setting temperature 24°C, Heating setting temperature 21°C.
S31/S32 displays “U005”, which is used to set setting temperature band.
1~9°C.
S31/S32 displays “U006-U009”, which are reserved to set parameters with optional accessory to
measure PM2.5 and CO2 values.
S31/S32 displays “U010~U011”, which are reserved.
S31/S32 displays “U012”, which is used to set setting RH point.
30~70, default: 50
S31/S32 displays “U013”, which is used to set setting RH band.
10~30, default: 10
Cooke Industries - Phone: +64 9 579 2185 Email: [email protected] Web: www.cookeindustries.co.nz