29
Diagram with heat buffer
4
, where: 1 – boiler, 2 – boiler pump, 3 – H1-S temperature sensor, 4 – heat buffer, 5 –
fireplace pump controlled by fireplace regulator, 6 – H0-S sensor, 7 – fireplace with water jacket, 8 – H2 CIRCUIT
regulated circuit water temperature sensor, 9 – H2 circuit pump, 10 –electrical servo of H2 CIRCUIT regulated heat circuit,
11 – fireplace regulator, 12 – plate heat exchanger, 13 –thermostatic valve protecting return temperature.
PROPOSED SETTINGS:
Parameter
Setting
MENU
Hydraulic diagram
3
menu
service settings
System
Selection
Fireplace
menu
service settings
System
Additional heat source
Temperature deactivating main
heat source
35
C
menu
service settings
System
Additional heat source
Pump starting temperature
55
C
menu
service settings
System
Additional heat source
Cooling temperature
92
C
menu
service settings
System
Additional heat source
Minimum temperature
25
C
menu
service settings
System
Main heat source
Description: Pump (2) works together with boiler (1). When boiler (1) switches off, pump (2) deactivates with 5
minute delay. After fireplace sensor (6) is heated up to a temperature of (35
C), boiler (1) and pump (2) deactivates
with 5 minute delay. Pump (5) is controlled by fireplace regulator (11). When (6) exceeds 92
C, heat excess will be
transferred to heat and HUW circuits. Pump (9) will switch off if temperature on sensor (3) drops below 25
C.
4
The hydraulic diagram shown does not replace the central heating system design and is used for illustrative purposes
only!
Summary of Contents for ecoMAX920P2-I
Page 2: ......
Page 6: ...6...
Page 7: ...CONTROLLER OPERATION MANUAL ecoMAX920P2 I FOR THE USER...
Page 18: ......
Page 19: ...CONTROLLER ASSEMBLY AND SERVICE SETTINGS MANUAL ecoMAX920P2 I FOR THE INSTALLER...
Page 47: ...47...
Page 48: ...ul Wsp lna 19 Ignatki 16 001 Kleosin Poland plum plum pl www plum pl...