background image

14 

 

 

periods  as  “day”  temperature. 
Circuit  is  off  outside  the  defined 
time  periods.  Anti  –  freeze 
function remains active provided 
that is in active in service menu. 
It  is  not  possible  to  select  this 
mode  for  HUW  tank.  Instead  of 
this  it  is  recommended  to  select 
“Off”  mode  +  1x  HUW  loading 
for HUW. 

Additional modes 

Outside 

 

Time mode. Enables to save heat 
energy  when  a  person  is  out. 
Away  time  is  set,  e.g.  3  hours. 
During 

this 

period 

room 

temperature  for  heat  circuits  is 
set  as  “night”.  HUW  tank  is 
turned  off.  After  the  set  time  is 
over,  system  switches  to  a 
previous work mode. Set outside 
time  to  0  in  order  to  switch  off 
this mode. 

Party 

 

Time  mode.  Enables  to  achieve 
full  heat  comfort  by  temporary 
activation  of  modes  responsible 
for saving heat energy. A time is 
set,  e.g.  5  hours.  During  this 
period  room  temperature  for 
heat  circuits  is  set  as  “day”.  
HUW  tank  is  loaded  to  a  set 
temperature.  After  the  set  time 
is  over,  system  switches  to  a 
previous  work  mode.  Set  party 
time  to  0  in  order  to  switch  off 
this mode. 

Airing 

 

Time mode. Enables to save heat 
energy  when  rooms  are  aired. 
Airing  time  is  set,  e.g.  6 
minutes.  After  the  set  time  is 
over,  system  switches  to  a 
previous  work  mode.  Set  party 
time  to  0  in  order  to  switch  off 
this  mode.  This  mode  has  no 
influence  on  operation  of  HUW 
tank. 

 

Enables  a  single  HUW  load  in 
situation  when  HUW  tank  heat 
energy  saving  mode  is  active. 

1  x  HUW 
loading 

 

User  can  select  main  mode  for 
HUW  tank  as  “Inactive”  and,  if 
necessary, activate an additional 
“1 x HUW loading” mode in order 
to  save  heat  energy  resulting 
from  stoppage  losses  of  HUW 
tank. 

This  mode  can  also  be  useful  in 
situation  when  “Auto”  mode  is 
selected for HUW tank and night 
decrease  is  in  progress.  “1  x 
HUW loading” mode can be used 
for a single loading of HUW tank 
regardless of a night decrease. 

Work  mode  can  be  selected  separately  for 
each  heating  circuit  and  separately  for  HUW 
tank. In case when many heating circuits are 
assigned  to  a  common  control  panel,  work 
mode  change  is  global  and  applies  to  all 
circuits  simultaneously.  “Auto-eco”  and 
“Night”  modes  are  not  available  for  HUW 
tank. 

8.6

 

Holiday planning 

The  controller  is  equipped  with  a 
function enabling to plan holiday, 
i.e. days during which the user is 
outside his home. 

menu 

 Basic settings  

 Holiday   

Enter holiday start and end date and set the 
Activation = off. 
During  a  set  period,  independently  of  the 
selected  work  mode,  the  controller  will 
maintain  a  room  preset  temperature 
corresponding to a set “night” value. 

menu 

 Basic settings  

 Holiday   

HUW tank will be off. 

8.7

 

Changing names   

It is possible to change a default 
name  of  the  control  panel  and 
names 

of 

heating 

circuits 

displayed in the controller. 
Control  panel  name  can  be 

changed in: 

 

Summary of Contents for ecoMAX920P2-I

Page 1: ...FOR CENTRAL HEATING SYSTEMS OPERATION AND INSTALLATION MANUAL Manual version 1 0_EN 05 2019 ecoSTER TOUCH ecoNET300 ecoNET apk www econet24 com ecoSTER TOUCH and internet module ecoNET300 are not par...

Page 2: ......

Page 3: ...ANTI FREEZE 15 9 3 ROOM TEMPERATURE STABILIZATION 16 9 4 SOLAR 17 9 5 INTERNET 17 FOR THE INSTALLER 19 10 CONTROLLER ASSEMBLY 20 10 1 GENERAL REQUIREMENTS 20 10 2 OUTPUT MODULE ASSEMBLY 20 10 3 TEMPER...

Page 4: ...ainst frozen central heating system Values of programmed parameters must be set in accordance with a particular building and hydraulic system The controller is not an intrinsically safe device It mean...

Page 5: ...over to a new user or owner 5 Used symbols The following graphical symbols are used in the manual useful information and tips useful information concerning property damage health or life threat for p...

Page 6: ...6...

Page 7: ...CONTROLLER OPERATION MANUAL ecoMAX920P2 I FOR THE USER...

Page 8: ...enables quick transportation of HUW to a bathroom or kitchen located far away Heating circuits The controller control the operation of one direct heating circuit radiator and two adjustable heating c...

Page 9: ...mbol of active heat source this symbol indicates that the boiler is active 7 Heating mode symbol possible options day and night 8 Preset room temperature it is set separately for day and night mode Pr...

Page 10: ...o get back to main window from every menu sublevel 3 Info button press to obtain detailed information concerning the parameter selected on a display 4 Press to enter service level for installer 7 6 In...

Page 11: ...11 7 7 User s main menu Caution particular menu positions can be invisible in case there is no appropriate sensor module or setting...

Page 12: ...HUW window click an arrow in controller main window element no 11 HUW preset temperature can be also entered in menu preset temperatures HUW tank loading function becomes active after connecting a ta...

Page 13: ...perature drops below SUMMER mode deact temperature parameter Automatic switching into SUMMER mode is possible only when the external temperature sensor is connected 8 5 Work mode setting It is possibl...

Page 14: ...nfluence on operation of HUW tank Enables a single HUW load in situation when HUW tank heat energy saving mode is active 1 x HUW loading User can select main mode for HUW tank as Inactive and if neces...

Page 15: ...rameters i e when the controller is operated Day screen brightness between 06 00 22 00 Night screen brightness between 22 00 06 00 8 11 Software update Software can be modified with the use of microSD...

Page 16: ...e pump will be stopped If it is lower than 13 C the pump will continue its operation and heating circuit will be heated by a heat source boiler up to a minimum value service parameter The pump will be...

Page 17: ...ank work mode to Auto Define time program for HUW tank in such way to set insolation periods as night Due to this the boiler will not heat up the HUW tank Similar effect can be obtained by setting the...

Page 18: ......

Page 19: ...CONTROLLER ASSEMBLY AND SERVICE SETTINGS MANUAL ecoMAX920P2 I FOR THE INSTALLER...

Page 20: ...ing provides the IP20 protection rating The casing on the connectors cover side provides IP00 rating and because of that connectors must be unconditionally covered with the cover If there is a need to...

Page 21: ...rcuit pumps to the controller according to the electric scheme 10 6 Connecting servos Electrical servo is installed only when there is an adjustable heating circuit H2 circuit or H3 circuit The contro...

Page 22: ...ong wall surface In service settings of each circuit assign the control panel to an appropriate heating circuit or a group of heating circuits for which it will serve as a room thermostat After the pa...

Page 23: ...nd 2 adjustable H2 circuit 3 adjustable H3 circuit 4 control panel no 2 5 boiler 6 controller output module Names of room panel and heating circuits can be changed Maximum 6 room panels can be connect...

Page 24: ...er it is recommended to increase heating curve parallel shift and decrease the heating curve if during frost room temperature is too low and too high when the weather is warmer it is recommended to de...

Page 25: ...correction 0 Room thermostat deactivation In order to cause room thermostat to influence the set temperature of water in the heat circuit set room temperature correction parameter to 0 when room therm...

Page 26: ...20 boiler with integrated pump 21 mechanical protective thermostat for protecting floor circuit against excessive water temperature 22 HUW tank lower temperature sensor lower solar sensor 23 solar col...

Page 27: ...ling main heat source 35 C menu service settings System Additional heat source Pump start temperature 8 55 C menu service settings System Additional heat source Minimum temperature 50 C menu service s...

Page 28: ...heat source Temperature deactivating main heat source 35 C menu service settings System Additional heat source Cooling temperature 92 C menu service settings System Additional heat source Minimum temp...

Page 29: ...C menu service settings System Additional heat source Pump starting temperature 55 C menu service settings System Additional heat source Cooling temperature 92 C menu service settings System Addition...

Page 30: ...settings System Main heat source Hysteresis heat source 5 C menu service settings System Main heat source Selection heat source boiler pellet menu service settings System Main heat source Pump operat...

Page 31: ...13 weather sensor 14 HUW pump 15 HUW tank water temperature sensor 16 HUW circulating pump 17 solar pump 18 solar panel 19 controller control panel with room thermostat function 20 mechanical protect...

Page 32: ...e setting System Main heat source Disabling the absence of heat demand YES menu service setting System Main heat source Selection Fireplace menu service setting System Additional heat source Pump star...

Page 33: ...e menu service setting System Additional heat source Temperature deactivating main heat source 35 C menu service setting System Additional heat source Pump starting temperature 55 C menu service setti...

Page 34: ...als 26 55 terminal RJ or USB will damage the controller and may cause electric shock Tips of connection cables especially mains voltage cables should be secured from splitting by e g insulated clamp s...

Page 35: ...ector 2 protective strip 3 placing cable clamps in the housing they should be broken 4 cable outlets 5 improper cable connection 6 holdfast of the cable Electrical cables should be isolated from hot p...

Page 36: ...g temperature of a fireplace with water jacket type CT 10 WS weather temperature sensor type CT6 P H0 S universal temperature sensor e g for measuring temperature of a heat buffer type CT 10 OUT V2 ou...

Page 37: ...e heating curve shift Constant water preset temperature Decreasing constant water temperature Room thermostat selection No Panel 1 T1 T3 Room thermostat function Thermostat Temperature correction Room...

Page 38: ...time Notifications Operation in HOLIDAY mode Solar Support Solar pump activation delta T Solar pump deactivation delta T Minimum collector temperature Maximum collector temperature Collector disable t...

Page 39: ...rom the control panel and they have an effect on a preset temperature of water in the heating circuit Name Panel 1 can be changed in the main menu to e g Living room in case the panel is assembled in...

Page 40: ...uit High temperature in the floor circuit can cause damage to flooring and scalding to users Adjustment method fixed value weather weather fixed value constant preset temperature of water in nonadjust...

Page 41: ...an be used only when Room thermostat function thermostat Exceeding a set room temperature causes decreasing set temperature in the heat circuit by Decreasing water temperature from thermostat value Se...

Page 42: ...loading at disabled heating circuits Extending HUW pump operation time 0 255 0 min After loading the HUW tank and disabling the HUW pump a risk of boiler overheat can occur Such risk is possible in a...

Page 43: ...n Modulation 5K Modulation 10K Modulation 20K No modulation Setting No modulation the main source of heat works without output modulation Setting Modulation 5K Modulation 10K Modulation 20K the main h...

Page 44: ...ps below Solar pump activation delta T parameter value solar pump will be deactivated Minimum collector temperature 4 110 10 C Solar pump will not be enabled below this temperature If minimum collecto...

Page 45: ...The settings for the buffer are only visible in the menu after selecting the supported hydraulic diagram no 6 Solar Name Range Setting Description Valve switching temperature 25 80 55 C Temperature a...

Page 46: ...adiation During transportation the controller cannot be subjected to vibrations exceeding normal vibrations generated during wheel transportation 9 It is a current consumed only by the controller Over...

Page 47: ...47...

Page 48: ...ul Wsp lna 19 Ignatki 16 001 Kleosin Poland plum plum pl www plum pl...

Reviews: