32
Diagram with heat buffer with layered charging buffer
7
, where: 1 – main controller module, 2- controller control
panel with room thermostat function, 3 – fireplace, 4 – heat buffer, 5 – automatic boiler, OUT-A – boiler pump, OUT-B –
fireplace pump, OUT-C - air valve open / close (optional), OUT-D - diverter valve (optional), S-P – solar pump, H1-P -
direct heating circuit pump, H2-P, H3-P - adjustable heating circuit pump, H2-M, H3-M - valve electrical servo of
adjustable circuit, C-P – circulation pump, H1-S - upper temperature sensor buffer, H4-S - center sensor buffer, H5-S –
exhaust temperature sensor (optional), SH - solar collector temperature sensor, SL – lower solar sensor, WS - weather
sensor, HDW - HUW tank temperature sensor (optional).
PROPOSED SETTINGS:
Parameter
Setting
MENU
Hydraulic diagram
6
menu
service setting
System
Pump starting temperature
50
C
menu
service setting
Buffer
Pump stoping temperature
26
C
menu
service setting
Buffer
Switching
valve
activation
temperature
55
C
menu
service setting
Buffer
Selection heat source
gas boiler
menu
service setting
System
Main heat source
Disabling the absence of heat
demand
YES
menu
service setting
System
Main heat source
Selection
Fireplace
menu
service setting
System
Additional heat source
Pump starting temperature
55
C
menu
service setting
System
Additional heat source
Description: After heating the sensor H0-S temperature (55
C) shall be attached to the pump (OUT-B). Pump (OUT-B)
operates only when the temperature H0-S is greater than the temperature of H1-S. Pump H1-P, H2-PH3-P will turn on
when the temperature H4-S reaches 50
C and turn off when the temperature H1-S falls below 25
C.
Boiler (5) turns on
when the temperature measured on the sensor H1-S is below the preset temperature, however, to turn on the boiler it
is necessary to decrease room temperature measured by the panel (2) below the preset. On the valve actuator (6) is
given an electrical voltage when the temperature measured on the sensor H4-S falling below 55
C (loading upper
buffer).
A valve actuator (6) is turned off when the temperature measured at the sensor H4-S rises above 55
C (loading
throughout the volume of buffer).
7
The hydraulic diagram shown does not replace the central heating system design and is used for illustrative purposes
only!
Summary of Contents for ecoMAX920P2-I
Page 2: ......
Page 6: ...6...
Page 7: ...CONTROLLER OPERATION MANUAL ecoMAX920P2 I FOR THE USER...
Page 18: ......
Page 19: ...CONTROLLER ASSEMBLY AND SERVICE SETTINGS MANUAL ecoMAX920P2 I FOR THE INSTALLER...
Page 47: ...47...
Page 48: ...ul Wsp lna 19 Ignatki 16 001 Kleosin Poland plum plum pl www plum pl...