36
14.7
Thermostat selection
SERVICE SETTINGS > BOILER SETTINGS
> Thermostat selection
This option enables selection of room
thermostat for boiler circuit in case ecoSTER
room control panel is connected or
mechanical
thermostats
connected
to
working module B are used. Following
options are available:
-
OFF
,
-
Standard 1
– standard NO/NC thermostat
connected to terminals 26-27 of module B,
-
Standard 2
– standard NO/NC thermostat
connected to terminals 28-29 of module B,
-
ecoSTER1
– thermostat 1 in ecoSTER,
-
ecoSTER2
– thermostat 2 in ecoSTER,
-
ecoSTER3
– thermostat 3 in ecoSTER.
If ecoSTER is not connected, only options
related to operation with standard room
thermostats are available in the menu.
14.8
Min. preset boiler temperature
This parameter is used to prevent the user to
set too low value of preset boiler
temperature. Boiler operation at too low
temperature may cause its quick damage,
corrosion, dirt, etc. The algorithms, which
automatically reduce the temperature, do not
cause the fall of preset boiler temperature
below the minimum value configurable in this
parameter.
Set this value acc. recommendation
of boiler manufacturer
14.9
Max. pre-set boiler temperature
This parameter is used to prevent the user to
set too high value of preset boiler
temperature.
The algorithms, which automatically increase
the temperature (correction acc. heating
curve or to required HUV temperature), do
not cause the increase of boiler temperature
above the maximum value configurable in
this parameter.
Set this value acc. recommendation
of boiler manufacturer.
14.10
Min. blow-in output
During first start-up of the boiler, set the
minimum blowing power, which may be
selected by the user.
SERVICE SETTINGS > BOILER SETTINGS
> Minimum blow-in output
This parameter protects the fan from
damage caused by operation with too low
rotary speed. Min. blowing power should be
set basing upon observations of fan
behaviour; some reserve should be also
considered.
Upon setting e.g. 20% the user will be able
to set the blowing power not less than 20%.
14.11
No fuel detection time
Lack of fuel in main boiler bin may be
detected by the regulator basing upon
exhaust temperature. In case the exhaust
temperature has been lower than the value
set in the parameter
SERVICE SETTINGS > BOILER SETTINGS
> Ex.temp.w.no fuel
over the time longer than the value set in the
parameter:
SERVICE SETTINGS > BOILER SETTINGS
> No fuel detection time
the regulator proceeds from OPERATION do
FIRING-UP. If there is no fuel in the bin,
FIRING-UP process will be concluded with a
message "furnace fire-up is impossible".
14.12
Maximum feeder temperature
It is the temperature at which the protection
against flashback to fuel feeder trips. This
function is described in sec. 22.3
Setting
Maximum
feeder
temperature
at
"0”
enables
disconnection of feeder sensor and
regulator operation without this
sensor. Nevertheless, this setting is
not
recommended
because
flashback prevention function is
disabled.
14.13
Poker cycle time
Poker operation is set in the parameter:
SERVICE SETTINGS > BOILER SETTINGS
> Poker cycle time