45
The
temperature
is
measured incorrectly.
Check if there is good thermal contact between the temperature
sensor and the measured surface,
Whether the sensor lead is not placed too close to the mains
cable,
If the sensor is connected to the terminal,
Whether the sensor is not damaged – check it in accordance with
point 13.11.
in
the
DHW=SUMMER
mode, the radiators are hot
and the boiler overheats.
Increase the parameter
DHW operation extend.
in order to cool
down the boiler.
the DHW pump is active
even if the DHW tank has
been filled.
Set the parameter
DHW operation extend
to
0
.
The
boiler
overheats
despite disabled airflow.
The reason can be faulty chimney installation (no protection
against excessive chimney draught).
In a hydraulic system with
a mixing valve and servo -
the mixer fails to open.
The reason can be that the DHW tank is being filled with
DHW
priority
enabled. Wait until the DHW is filled, or disable the
DHW
priority
.
The reason can be active SUMMER function.
The reason can be an on-going calibration of the mixer valve,
wait until the calibration is complete. Active calibration is
signalled with a “CAL” message in the menu INFORMATION –
MIXER INFO.
26
Regulator setup by boiler manufacturer.
CAUTION: THE INDIVIDUAL FUZZY LOGIC PROGRAM IS SELECTED INDIVIDUALLY TO
THE GIVEN BOILER TYPE. MAKE SURE THAT THE FITTINGS FOR BOILERS TESTED IN
THE PLUM LABORATORIES ARE COMPATIBLE WITH FITTINGS FOR SOLD BOILERS. IT IS
INADMISSIBLE TO REPLACE THE FEEDER AND FAN TO OTHER TYPES AS WELL AS
MAKING OTHER CONSTRUCTIONAL MODIFICATIONS WHICH CAN HAVE IMPACT ON
COMBUSTION PROCESS.
26.1
Activating Individual Fuzzy Logic and changing boiler type
In order to activate the Individual Fuzzy Logic mode, enter menu:
Boiler settings> Output modulation > Regulation mode
In
this menu, find and confirm Individual Fuzzy Logic mode If the boiler operation modes list is
unavailable, and clicking the aforementioned menu triggers a message “Function unavailable”, it
means that the regulator operates only in the STANDARD mode, Individual Fuzzy Logic control is
disabled and unavailable for the given setup of a boiler.
To change the type of boiler, furnace, enter hidden menu:
Service settings >
[enter special password]
The special password is made available only to boiler manufacturers and authorized fitters.
Caution: selecting an incorrect boiler type, which was not examined in the
PLUM laboratories, can damage the boiler during its operation.
Settings for individual boilers require arrangements between the boiler manufacturer and the
PLUM sp. z o.o. company.
In order to apply the changes, it is necessary to disconnect and reconnect the regulator mains
supply.
Summary of Contents for ecoMAX810P3-L TOUCH
Page 2: ......
Page 8: ...8 REGULATOR INSTRUCTION MANUAL ecoMAX810P3 L TOUCH...
Page 20: ...REGULATOR INSTALLATION AND SERVICE SETTINGS MANUAL ecoMAX810P3 L TOUCH...
Page 46: ......
Page 47: ...47...