The  regulator  relates  the  setting  to  20 °C, 
e.g.  for  preset  room  temperature  =  22 °C, 
the regulator will translate the heating curve 
by  2°C,  for  preset  room  temperature  = 
18 °C, the regulator will translate the heating 
curve 

by 

-2 °C.

 

In some cases described in point 8.17, 

it may be necessary to fine-tune the heating 
curve translation. 
 
In  this  setup,  the  ecoSTER200  room 
thermostat can: 
- decrease the heating cycle temperature by 
a  constant  value  when  the  preset  room 
temperature  is  reached.  Analogously,  as 
specified  in  the  previous  point  (not 
recommended), or 
-  automatically,  continuously  correct  the 
heating cycle temperature.  

It  is  not  recommended  to  use  both 
options at the same time.  

 
Automatic correction of room temperature is 
carried  out  in  accordance  with  the  following 
formula: 

Correction  =  (Preset  room  temperature  - 
measured  room  temperature)  x  room 
temperature coefficient /10   

Example.  
Preset  temperature  in  the  heated  room  (set 
at  ecoSTER200)  =  22 °C.  Temperature 
measured  in  the  room  (by  ecoSTER200)  = 
20 °C.  

Room temp. coeff.

 =

 15. 

Preset  mixer  temperature  will  be  increased 
by (22 °C - 20 °C) x 15/10 = 3 °C. 
It  is  necessary  to  find  appropriate  value  of 
the 

Room  temp.  coeff.

  Range:  0…50.  The 

higher  the  coefficient,  the  greater  the 
correction  of  preset  boiler  temperature.  If 
the  setting  is  “0”,  the  preset  mixer 
temperature  is  not  corrected.  Note:  setting  
a  value  of  the  room  temperature  coefficient 
too  high  may  cause  cyclical  fluctuations  of 
the room temperature! 

8.17

 

Weather controlled operation 

Depending  on  the  temperature  measured 
outside  the  building,  both  preset  boiler 
temperature  and  temperatures  of  mixer 
circuits  can  be  controlled  automatically.  If 
proper  heating  curve  is  selected,  the 

temperature  of  the  circuits  is  calculated 
automatically,  depending  on  the  outdoor 
temperature.  Thus,  if  the  selected  heating 
curve  is  appropriate  for  the  given  building, 
the room temperature stays more or less the 
same, regardless of the temperature outside.  

 
Note: 

during  trial  and  error  selection  of 

appropriate  heating  curve,  it  is  necessary  to 
exclude influence of the room thermostat on 
regulator  operation  (regardless  of  whether 
the room thermostat is connected or not), by 
setting the parameter: 

Mixer 1 settings > Mixer room therm. 

to 

“0”. 
If a room panel ecoSTER200 is connected, it 
is also necessary to set the parameter 

Room 

temp. coeff.

 to “0”. 

 

Guidelines  for  proper  setting  of  the  heating 
curve: 

 

floor heating   

0,2 -0,6 

 

radiator heating  

1,0 - 1,6 

 

boiler   

 

1,8 - 4 

 

 

Fig. 5 Heating curves. 

Guidelines  for  selection  of  appropriate 
heating curve: 
-  if  the  outdoor  temperature  drops,  and  the 
room  temperature  increases,  the  selected 
heating curve value is too high, 
-  if  the  outdoor  temperature  drops,  and  the 
room temperature drops as well, the selected 
heating curve value is too low, 
-  if  during  frosty  weather  the  room 
temperature  is  proper,  but  when  it  gets 
warmer - it is too low, it is recommended to 
increase the 

Curve translation

 

and to select a 

lower heating curve, 

Summary of Contents for ecoMAX810P3-L TOUCH

Page 1: ...ich are available in modules respectively A B C SERVICE AND ASSEMBLY MANUAL ISSUE v1 1 APPLICABLE TO SOFTWARE MODULE A MODULE B PANEL v04 30 v04 30 v04 Boiler regulator ecoMAX810P3 L TOUCH FOR PELLET...

Page 2: ......

Page 3: ...other changes in the boiler fittings which can influence the burning process The fittings should correspond to the components installed by the manufacturer p 26 It is recommended to operate boiler wit...

Page 4: ...3 9 CONNECTION OF TEMPERATURE SENSORS 30 13 10 CONNECTION OF WEATHER SENSOR 30 13 11 TESTING OF TEMPERATURE SENSORS 30 13 12 CONNECTION OF MIXERS ROOM THERMOSTAT 31 13 13 CONNECTION OF RESERVE BOILER...

Page 5: ...CONTAINER LOADING 42 22 9 FAN DAMAGE 42 23 OTHERS 42 23 1 POWER FAILTURE 42 23 2 ANTI FREEZING PROTECTION 42 23 3 PROTECTION OF PUMPS AGAINST CLOGGING 42 24 REPLACEMENT OF PARTS AND COMPONENTS 42 24...

Page 6: ...gulator a boiler manufacturer should check if the regulator s mating with the given boiler type is proper and whether it can cause danger The regulator is not an intrinsically safe device which means...

Page 7: ...ters It can be used in a household and similar facilities as well as in light industrialized facilities 3 Information about documentation The regulator manual is a supplement for the boiler manual In...

Page 8: ...8 REGULATOR INSTRUCTION MANUAL ecoMAX810P3 L TOUCH...

Page 9: ...ction Automatic detection SUMMER mode SUMMER mode act temperature SUMMER mode deact temperature Night time decrease HUW HUW pump mode OFF Priority No priority Summer Mixer 1 4 settings Preset mixer te...

Page 10: ...ing increase of preset boiler temperature by mixer circuit increase of preset temperature for buffer loading Both left and right windows may display different information By touching the screen you ma...

Page 11: ...led regulator attempts to clean the furnace and fire it up poker is activated to operate over Poker cycle time fuel is supplied over Feeding time fan turns on with the power set in the parameter of Bl...

Page 12: ...by the boiler manufacturer in accordance with sec 26 1 In case this mode has not been activated when attempting to change the mode a prompt FUNCTION NOT AVALAIBLE appears Change of settings of Individ...

Page 13: ...the case of Standard control mode upon reaching preset boiler temperature during Individual Fuzzy Logic control upon exceeding the preset boiler temperature by 5 C In the Individual Fuzzy Logic mode...

Page 14: ...boiler is put out and awaits signal to resume heating A signal to start heating can be decrease in preset boiler temperature below the preset temperature minus the value of boiler hysteresis Boiler hy...

Page 15: ...nnecting room thermostat it is necessary to set a value of decrease in preset mixer temperature by thermostat parameters Mixer room therm e g at 5 C This value should be selected by trial and error Th...

Page 16: ...coefficient too high may cause cyclical fluctuations of the room temperature 8 17 Weather controlled operation Depending on the temperature measured outside the building both preset boiler temperature...

Page 17: ...ervals set the parameter Night time decrease for the given heating circuit at ON Night time decrease may be set separately for working days Saturdays and Sundays Fig 6 Time interwal setting window Sel...

Page 18: ...onding to 100 level of the fuel tank and set 100 level as described above Description of operation The regulator calculates the fuel level basing on the current fuel consumption Default settings do no...

Page 19: ...ON Note Long term operation of the fan the feeder or other working equipment may lead to occurrence of hazardous conditions 8 24 Operation in accordance with the schedule The boiler may be set to sta...

Page 20: ...REGULATOR INSTALLATION AND SERVICE SETTINGS MANUAL ecoMAX810P3 L TOUCH...

Page 21: ...Blow in output 100 Feeder operation 100 Feeder interval 50 Blow in output 50 Feeder operation 50 Feeder interwal 30 Blow in output 30 Feeder operation 30 Feeder interval Burning off Buring off time Ai...

Page 22: ...W pump 12 start once the boiler temperature has exceeded CH pump activation temperature usually 40 C In case the water which flows to the boiler is cold thermostatic valve 7 closes It causes the flow...

Page 23: ...ting floor heating 55 C 26 room thermostat of mixer 3 27 mixer temperature sensor 3 28 mixer servo 4 29 mixer pump 4 30 room thermostat of mixer 4 31 mixer temperature sensor 4 32 extension mixer modu...

Page 24: ...15 65 C During transport the device cannot be exposed to vibrations greater than those typical of normal road transport 13 MOUNTING REQUIREMENTS Basic version of the equipment is composed of three mod...

Page 25: ...ided Assembly shall assure IP rating appropriate to the environment conditions in which the regulator will operate Moreover access of the user to live parts under hazardous voltage e g terminals shall...

Page 26: ...herefore the terminals of working module have to be isolated and access to this section of the housing must be prevented To get access to the terminals disconnect power supply make sure terminals and...

Page 27: ...Wire ending protection a correct b incorrect Connect power supply wires to terminals indicated with an arrow 13 8 Protective connection Connect protective wire of power supply cable to ground strip li...

Page 28: ...ring diagram of sensors for A and B module For safety reasons the regulator shall be equipped with the set of pins inserted to 230 VAC power supply connectors even in case no load is connected to the...

Page 29: ...ature sensor type CT4 T room thermostat use only two wires for connection do not make connection using four wires risk of regulator damage A ecoMAX810P3 L TOUCH main regulator P3 power supply cable 23...

Page 30: ...allow sensor wires to contact hot parts of the boiler and heating system Wires of temperature sensors are heat resistant to the temperature not exceeding 100 C 13 10 Connection of weather sensor Regul...

Page 31: ...ttings see sec 8 16 13 13 Connection of reserve boiler Regulator may control reserve oil or gas fired boiler In such case manual start and stop of reserve boiler is not necessary Reserve boiler starts...

Page 32: ...to use reserve boiler In OFF mode control of CH system is disabled mixer HUW and boiler pumps and mixer control are inactive Fig 22 Hydraulic diagram with reserve boiler connection of open and close...

Page 33: ...should signal few selected alarms e g AL2 and AL4 alarms sum up the values indicated in the table for individual alarms i e 2 8 10 and set this parameter at this value If any of the alarms AL1 AL2 AL3...

Page 34: ...boiler Acc recent regulations use of safety temperature limiters is mandatory 13 18 Connection of room control panel Regulator may be equipped with ecoSTER TOUCH room control panel which may perform f...

Page 35: ...time of fuel feeding and fan operation in SUPERVISION mode see sec 8 8 Setting this parameter at 0 causes that only fan will be ON in SUPERVISION mode Value of this parameter may not be too high beca...

Page 36: ...e above the maximum value configurable in this parameter Set this value acc recommendation of boiler manufacturer 14 10 Min blow in output During first start up of the boiler set the minimum blowing p...

Page 37: ...slower the boiler temperature approaches the preset value Setting higher value gives more probability that oscillations of preset boiler temperature will not occur Too low value may cause instability...

Page 38: ...an preset boiler temperature 15 7 Heat exchanger When the parameter Heat exchanger is set at YES CH pump does not stop when HUW priority is set nor in HUW SUMMER mode This parameter is intended only f...

Page 39: ...ed other values 16 5 Proportional range Note Change of this parameter is not recommended It is the value of mixer stroke The higher the value is the faster the mixer circuit achieves the preset value...

Page 40: ...ambda sensor Note do not set too high values because it may adversely affect regulation process Parameters A B C Lambda affect the adjustment speed of oxygen value present in exhaust to the preset oxy...

Page 41: ...ps the feeder and does not activate it again even though the feeder temperature remains high Alarm may be reset only upon drop of feeder temperature To reset the alarm press encoder knob or switch off...

Page 42: ...tion stops Note the function of fan rotation detection has to be enabled by the boiler manufacturer 23 OTHERS 23 1 Power failture In case of power failure the regulator returns to the operation mode i...

Page 43: ...y cause incorrect operation of the regulator 24 3 Replacement of working module The requirements are the same as for the replacement of control panel see sec 24 2 24 4 Software up grade To up grade th...

Page 44: ...ion unlock it by removing the lid and pushing the button in accordance with the documentation provided by the boiler manufacturer check the fan and replace it if necessary Fuel feeder inoperative fail...

Page 45: ...VIDUAL FUZZY LOGIC PROGRAM IS SELECTED INDIVIDUALLY TO THE GIVEN BOILER TYPE MAKE SURE THAT THE FITTINGS FOR BOILERS TESTED IN THE PLUM LABORATORIES ARE COMPATIBLE WITH FITTINGS FOR SOLD BOILERS IT IS...

Page 46: ......

Page 47: ...47...

Page 48: ...Ignatki 27a 16 001 Kleosin Poland tel 48 85 749 70 00 fax 48 85 749 70 14 plum plum pl www plum pl www plumelectronics eu...

Reviews: