background image

14 

 

 

 

Parameters

 

should  be  selected  in 

such 

way, 

that 

boiler 

temperature 

would 

gradually 

decrease when this mode is active. 
Improper  settings  can  cause  the 
boiler to overheat  

 

Airflow  in  the  SUPERVISION  mode 
operates  with  power  set  in  the  power 
modulation  parameter 

30%  Airflow

 

power

The  regulator  returns  to  the  OPERATION 
mode  automatically  after  boiler  temperature 
decreases by the value of 

boiler hysteresis 

in 

relation to the preset temperature. 
Maximum  boiler  operation  time  in  the 
supervision mode is defined by parameter:

 

... > Supervision > Supervision time  

If  after  lapse  of  this  time  from  the  moment 
of  the  regulator’s  entering  the  supervision 
mode,  there  is  no  need  to  reactivate  the 
boiler,  the  regulator  will  commence  the 
process of putting the boiler out. 
 

8.9

 

BURNING OFF 

In  BURNING  OFF  mode,  rest  of  pellets  is 
burnt and boiler is being prepared to stop or 
shut-down. 
All  parameters,  which  affect  burning-off 
process are grouped in the menu: 

SERVICE SETTINGS > BOILER SETTINGS 
> BURNING OFF

 

Detailed description of burning-off cycle: 

 

Fuel feeder stops, 

 

Remaining fuel is burnt  – the  fan turns  on 
for the time set in 

Burning-off time

 with the 

power  set  in  the  parameter  of 

Air  flush 

intensity

 

 

The furnace is cleaned - poker switches on. 

 
Upon automatic burning-off, regulator enters 
STANDSTILL mode. 

8.10

 

STANDSTILL 

In  the  STANDSTILL  mode,  the  boiler  is  put 
out and awaits signal to resume heating.  
A signal to start heating can be:   

 

decrease  in  preset  boiler  temperature 
below  the  preset  temperature  minus  the 
value 

of 

boiler 

hysteresis 

(

Boiler 

hysteresis

),  

 

if  the  boiler  is  set  to  work  with  a  buffer  - 
decrease  in  upper  buffer  temperature 
below  the  preset  value  (Loading  start 
temperature). 

 

8.11

 

Domestic how water settings 

DHW 

The  device  controls  temperature  of  the 
domestic how water - DHW – tank, provided 
that  a  DHW  temperature  sensor  is 
connected.  If  the  sensor  is  disconnected,  an 
information about lack thereof is displayed in 
the main window. The parameter: 

HUW settings > HUW pump mode 

 allows 

the user to: 

 

disable 

filling

 

of

 

the

 

tank,

 

parameter

 

off,

 

 

set  DHW  priority,  using  the 

priority

 

parameter - in this case, the CH pump 
is  deactivated  to  speed  up  filling  of 
the DHW tank. 

 

set  simultaneous  operation  of  the  CH 

and  DHW  pump,  using  parameter 

no

 

priority

,

 

 

enable the 

summer

 function. 

8.12

 

Setting preset DHW temperature 

Preset  DHW  temperature  is  defined  by 
parameter:  

DHW settings > Preset DHW temp. 
 

8.13

 

DHW tank hysteresis 

Below  temperature 

DHW  preset  temp. 

reduced  by

  DHW  tank  hysteresis, 

the  DHW 

pump  is  activated  in  order  to  fill  the  DHW 
tank. 
 

 

When  value  of  hysteresis  is  set  too 
low, the DHW pump will start faster 
after decrease in DHW temperature. 

 

8.14

 

Enabling the SUMMER function 

In  order  to  activate  the  SUMMER  function, 
which  enables  to  load  the  DHW  tank  in  the 
summer, without the need  for activating the 
CH  system  and  mixer  cycles,  set  the 
parameter 

DHW  pump  operation  mode 

to 

summer. 

 

Summary of Contents for ecoMAX810P3-L TOUCH

Page 1: ...ich are available in modules respectively A B C SERVICE AND ASSEMBLY MANUAL ISSUE v1 1 APPLICABLE TO SOFTWARE MODULE A MODULE B PANEL v04 30 v04 30 v04 Boiler regulator ecoMAX810P3 L TOUCH FOR PELLET...

Page 2: ......

Page 3: ...other changes in the boiler fittings which can influence the burning process The fittings should correspond to the components installed by the manufacturer p 26 It is recommended to operate boiler wit...

Page 4: ...3 9 CONNECTION OF TEMPERATURE SENSORS 30 13 10 CONNECTION OF WEATHER SENSOR 30 13 11 TESTING OF TEMPERATURE SENSORS 30 13 12 CONNECTION OF MIXERS ROOM THERMOSTAT 31 13 13 CONNECTION OF RESERVE BOILER...

Page 5: ...CONTAINER LOADING 42 22 9 FAN DAMAGE 42 23 OTHERS 42 23 1 POWER FAILTURE 42 23 2 ANTI FREEZING PROTECTION 42 23 3 PROTECTION OF PUMPS AGAINST CLOGGING 42 24 REPLACEMENT OF PARTS AND COMPONENTS 42 24...

Page 6: ...gulator a boiler manufacturer should check if the regulator s mating with the given boiler type is proper and whether it can cause danger The regulator is not an intrinsically safe device which means...

Page 7: ...ters It can be used in a household and similar facilities as well as in light industrialized facilities 3 Information about documentation The regulator manual is a supplement for the boiler manual In...

Page 8: ...8 REGULATOR INSTRUCTION MANUAL ecoMAX810P3 L TOUCH...

Page 9: ...ction Automatic detection SUMMER mode SUMMER mode act temperature SUMMER mode deact temperature Night time decrease HUW HUW pump mode OFF Priority No priority Summer Mixer 1 4 settings Preset mixer te...

Page 10: ...ing increase of preset boiler temperature by mixer circuit increase of preset temperature for buffer loading Both left and right windows may display different information By touching the screen you ma...

Page 11: ...led regulator attempts to clean the furnace and fire it up poker is activated to operate over Poker cycle time fuel is supplied over Feeding time fan turns on with the power set in the parameter of Bl...

Page 12: ...by the boiler manufacturer in accordance with sec 26 1 In case this mode has not been activated when attempting to change the mode a prompt FUNCTION NOT AVALAIBLE appears Change of settings of Individ...

Page 13: ...the case of Standard control mode upon reaching preset boiler temperature during Individual Fuzzy Logic control upon exceeding the preset boiler temperature by 5 C In the Individual Fuzzy Logic mode...

Page 14: ...boiler is put out and awaits signal to resume heating A signal to start heating can be decrease in preset boiler temperature below the preset temperature minus the value of boiler hysteresis Boiler hy...

Page 15: ...nnecting room thermostat it is necessary to set a value of decrease in preset mixer temperature by thermostat parameters Mixer room therm e g at 5 C This value should be selected by trial and error Th...

Page 16: ...coefficient too high may cause cyclical fluctuations of the room temperature 8 17 Weather controlled operation Depending on the temperature measured outside the building both preset boiler temperature...

Page 17: ...ervals set the parameter Night time decrease for the given heating circuit at ON Night time decrease may be set separately for working days Saturdays and Sundays Fig 6 Time interwal setting window Sel...

Page 18: ...onding to 100 level of the fuel tank and set 100 level as described above Description of operation The regulator calculates the fuel level basing on the current fuel consumption Default settings do no...

Page 19: ...ON Note Long term operation of the fan the feeder or other working equipment may lead to occurrence of hazardous conditions 8 24 Operation in accordance with the schedule The boiler may be set to sta...

Page 20: ...REGULATOR INSTALLATION AND SERVICE SETTINGS MANUAL ecoMAX810P3 L TOUCH...

Page 21: ...Blow in output 100 Feeder operation 100 Feeder interval 50 Blow in output 50 Feeder operation 50 Feeder interwal 30 Blow in output 30 Feeder operation 30 Feeder interval Burning off Buring off time Ai...

Page 22: ...W pump 12 start once the boiler temperature has exceeded CH pump activation temperature usually 40 C In case the water which flows to the boiler is cold thermostatic valve 7 closes It causes the flow...

Page 23: ...ting floor heating 55 C 26 room thermostat of mixer 3 27 mixer temperature sensor 3 28 mixer servo 4 29 mixer pump 4 30 room thermostat of mixer 4 31 mixer temperature sensor 4 32 extension mixer modu...

Page 24: ...15 65 C During transport the device cannot be exposed to vibrations greater than those typical of normal road transport 13 MOUNTING REQUIREMENTS Basic version of the equipment is composed of three mod...

Page 25: ...ided Assembly shall assure IP rating appropriate to the environment conditions in which the regulator will operate Moreover access of the user to live parts under hazardous voltage e g terminals shall...

Page 26: ...herefore the terminals of working module have to be isolated and access to this section of the housing must be prevented To get access to the terminals disconnect power supply make sure terminals and...

Page 27: ...Wire ending protection a correct b incorrect Connect power supply wires to terminals indicated with an arrow 13 8 Protective connection Connect protective wire of power supply cable to ground strip li...

Page 28: ...ring diagram of sensors for A and B module For safety reasons the regulator shall be equipped with the set of pins inserted to 230 VAC power supply connectors even in case no load is connected to the...

Page 29: ...ature sensor type CT4 T room thermostat use only two wires for connection do not make connection using four wires risk of regulator damage A ecoMAX810P3 L TOUCH main regulator P3 power supply cable 23...

Page 30: ...allow sensor wires to contact hot parts of the boiler and heating system Wires of temperature sensors are heat resistant to the temperature not exceeding 100 C 13 10 Connection of weather sensor Regul...

Page 31: ...ttings see sec 8 16 13 13 Connection of reserve boiler Regulator may control reserve oil or gas fired boiler In such case manual start and stop of reserve boiler is not necessary Reserve boiler starts...

Page 32: ...to use reserve boiler In OFF mode control of CH system is disabled mixer HUW and boiler pumps and mixer control are inactive Fig 22 Hydraulic diagram with reserve boiler connection of open and close...

Page 33: ...should signal few selected alarms e g AL2 and AL4 alarms sum up the values indicated in the table for individual alarms i e 2 8 10 and set this parameter at this value If any of the alarms AL1 AL2 AL3...

Page 34: ...boiler Acc recent regulations use of safety temperature limiters is mandatory 13 18 Connection of room control panel Regulator may be equipped with ecoSTER TOUCH room control panel which may perform f...

Page 35: ...time of fuel feeding and fan operation in SUPERVISION mode see sec 8 8 Setting this parameter at 0 causes that only fan will be ON in SUPERVISION mode Value of this parameter may not be too high beca...

Page 36: ...e above the maximum value configurable in this parameter Set this value acc recommendation of boiler manufacturer 14 10 Min blow in output During first start up of the boiler set the minimum blowing p...

Page 37: ...slower the boiler temperature approaches the preset value Setting higher value gives more probability that oscillations of preset boiler temperature will not occur Too low value may cause instability...

Page 38: ...an preset boiler temperature 15 7 Heat exchanger When the parameter Heat exchanger is set at YES CH pump does not stop when HUW priority is set nor in HUW SUMMER mode This parameter is intended only f...

Page 39: ...ed other values 16 5 Proportional range Note Change of this parameter is not recommended It is the value of mixer stroke The higher the value is the faster the mixer circuit achieves the preset value...

Page 40: ...ambda sensor Note do not set too high values because it may adversely affect regulation process Parameters A B C Lambda affect the adjustment speed of oxygen value present in exhaust to the preset oxy...

Page 41: ...ps the feeder and does not activate it again even though the feeder temperature remains high Alarm may be reset only upon drop of feeder temperature To reset the alarm press encoder knob or switch off...

Page 42: ...tion stops Note the function of fan rotation detection has to be enabled by the boiler manufacturer 23 OTHERS 23 1 Power failture In case of power failure the regulator returns to the operation mode i...

Page 43: ...y cause incorrect operation of the regulator 24 3 Replacement of working module The requirements are the same as for the replacement of control panel see sec 24 2 24 4 Software up grade To up grade th...

Page 44: ...ion unlock it by removing the lid and pushing the button in accordance with the documentation provided by the boiler manufacturer check the fan and replace it if necessary Fuel feeder inoperative fail...

Page 45: ...VIDUAL FUZZY LOGIC PROGRAM IS SELECTED INDIVIDUALLY TO THE GIVEN BOILER TYPE MAKE SURE THAT THE FITTINGS FOR BOILERS TESTED IN THE PLUM LABORATORIES ARE COMPATIBLE WITH FITTINGS FOR SOLD BOILERS IT IS...

Page 46: ......

Page 47: ...47...

Page 48: ...Ignatki 27a 16 001 Kleosin Poland tel 48 85 749 70 00 fax 48 85 749 70 14 plum plum pl www plum pl www plumelectronics eu...

Reviews: