When choosing an improper combination of
these parameters (e.g. the number of pulses
per time unit cannot be generated due to the
pulse width which is too large), one of the fol-
lowing error messages will be displayed.:
Pulse width
inconsistent
too large
parameters
For selecting the desired function please use
the key
▲
or
▼
. After choosing the function
output of pulses
or
frequency
and pressing
Enter, the following selection field will be dis-
played.
Output of
[pulses]
Example:
Pulse output unit:
This function is used to define the unit to be ac-
cumulated.
After selecting the function Pulse output unit,
press Enter to enter the parameter level. The
following selection field will be displayed:
Accumulation
of [ m3 ]
Example:
For this parameter the following units are avail-
able:
Volume units:
m3
Cubic metre
l
Litre
USG
Gallon (US)
UKG
Gallon (brit.)
ft3
Cubic feet
Mass units:
kg
Kilogram
t
Tonne
Pulse value:
This function is used to define how many pulses
will be output per accumulated unit.
After selecting the function
Pulse value
, press
the ENTER key to display the current unit:
1 pulse per
001.000 unit
Example:
Pulse width:
This function is intended to change the width of
the pulses.
For selecting the desired function please use
the key
or
. After selecting the function
Pulse width, press Enter to display the actual
setting for this parameter:
Pulse width
0050.0 ms
Example:
If the pulse width for the actual pulse number is
selected too high, the warning message "Value
too high" appears and the changes are not ap-
plied.
The maximum output frequency f can be calcu-
lated by
1000Hz
[ms]
width
pulse
2
1
f
Notice
For connection of electronic counters,
we recommend a pulse width greater
than 4 ms; for electromechanical counters the
value should be 50 ms.
Technical changes reserved
-