7.5 Additional prescriptions for safety applications with operator protection 
functions

Provided that all previous requirements for the devices are fulfilled, for installations 
with operator protection function additional requirements must be observed.
- The utilization implies knowledge of and compliance with following standards: 
EN ISO 13849-1, EN 62061, EN 60204-1, EN ISO 12100. 
- In the risk analysis, take into account that in manual start mode a possible sticking of 
the start button can lead to an immediate activation of the module.
- If external expansion modules or contactors are used to expand the system's switch-
ing capacity, check the contacts of these devices are forcibly guided. Also use an NC 
contact on each device to detect, through a feedback circuit, its correct operation (see 
examples) in particular to detect if any contacts are sticking.

7.6 Limits of use

- Use the device following the instructions, complying with its operation limits and the 
standards in force.
- The devices have specific application limits (min. and max. ambient temperature, 
maximum currents, IP protection degree, etc.) These limitations are met by the device 
only if considered individually and not as combined with each other. 
- According to EU directives, this device is not intended for private use.
- The manufacturer’s liability is to be excluded in the following cases:
1) Use not conforming to the intended purpose.
2) Failure to adhere to these instructions or regulations in force.
3) Fitting operations not carried out by qualified and authorized personnel.
4) Omission of functional tests.
- For the cases listed below, before proceeding with the installation contact our as-
sistance service (see paragraph SUPPORT):
a) In nuclear power stations, trains, airplanes, cars, incinerators, medical devices or 
any application where the safety of two or more persons depend on the correct opera-
tion of the device.
b) Applications not contemplated in this instruction manual.

 8 MARKINGS

The outside of the device is provided with external marking positioned in a visible 
place. Marking includes:
- Producer trademark
- Product code
- Batch number and date of manufacture. Example: CS1-123456 (A20). The last part 
of the production batch refers to the month of manufacture (A = January, B = February, 
etc.) as well as the year of manufacture (20 = 2020, 21 = 2021, etc.).

 9 TECHNICAL DATA

9.1 Housing

Material: Polyamide PA 66, self-extinguishing V0 acc. to UL 94
Protection degree: 

IP40 (housing), IP20 (terminal strip)

Cable cross section: 

0.2 … 2.5 mm

 (24 … 12 AwG)

Terminal tightening torque: 

0.5 … 0.6 Nm

9.2 General data

SIL (SIL CL): 

Up to SIL CL 3 acc. to EN 62061

Performance Level (PL):  

Up to PL e acc. to EN ISO 13849-1

Safety category: 

Up to cat. 4 acc. to EN ISO 13849-1

MTTF

D

:  

288 years

DC:  

high

PFh

D

3.46 E-09

Mission time: 

20 years

Ambient temperature: 

-25°C … +55°C

Storage temperature: 

-25°C … +70°C

Pollution degree: 

external 3, internal 2

Impulse withstand voltage U

imp

0.8 kV

Rated insulation voltage U

i

32 V

Overvoltage category: 

II

Air and surface distances:  

acc. to EN 60947-1

9.3 Power supply (A1-A2)

Rated supply voltage U

n

:  

24 Vdc

Supply voltage tolerance:  

±15% of U

n

Max. residual ripple: 

10%

Rated consumption (w/o load): 

< 3 w

Internal general protection: 

PTC, Ih=1.5 A

PTC response time: 

response time > 100 ms, release time > 3 s

Internal protection against short circuits on outputs (Tx, Ox): electronic
Maximum current output of the module as the total current of the Ox and Tx outputs: 
 

0.5 A

Self-test duration on startup: 

< 2 s

9.4 Input circuits (Ix)

Number of inputs:  

8

Voltage and current in the input circuits:   24 V, 5 mA
Input signals: 

0-8 V (Off), 12-24 V (On)

Galvanic separation: 

no

Minimum duration of input signal: 

10 ms

Input signal filtering:  

yes, maximum interference period 0.4 ms

Maximum input resistance: 

100 

Ω

Maximum input capacitance: 

470 nF to ground 

 

470 nF between two conductors

9.5 Decoupled input circuits (Jx)

Number of inputs:  

8

Voltage and current in the input circuits:   24 V, 5 mA
Input signals: 

0-8 V (Off), 12-24 V (On)

Galvanic separation: 

yes

Insulation voltage (U

i

): 

500 V

Minimum duration of input signal: 

10 ms

Input signal filtering: 

yes, maximum interference period 0.4 ms

Maximum input resistance: 

100 

Ω

Maximum input capacitance: 

470 nF to ground

 

470 nF between two conductors

NB: Voltage and current values indicated refer to the power supply terminals (Ax, see each module 
individually) of the board where the Jx type terminals are present

9.6 Frequency input circuits (Fx)

Number of inputs:  

8

Rated supply voltage: 

24 Vdc ± 15 %

Input circuit voltage and current:  

24 Vdc, 7 mA

Check of the supply voltage of the connected proximity sensors: 
 

24 Vdc ± 20%

Maximum detectable frequency: 

4 khz

Minimum detectable frequency: 

1 hz

Frequency detection accuracy:  

1 % ± 1 digit

Resolution: 

0.1 hz

Minimum time for standstill detection:  

1 s

Galvanic separation: 

yes

Insulation voltage (U

i

): 

500 V

NB: Voltage and current values indicated refer to the power supply terminals (Ax, see each module 
individually) of the board where the Fx type terminals are present

9.7 Circuits with Test signals (Tx)

Number of test signals: 

4

Signal type: 

pulsed 100 hz 24V/0V, duty cycle 50% 

Max. current per test signal: 

0.2 A

Max. total current: 

See Power supply (A1-A2)

Protected against short circuit: 

yes

Galvanic separation: 

no

9.8 Semiconductor signalling output circuits (Ox) 

Number of outputs:  

4

Output type: 

PNP

Maximum current per output: 

0.5 A

Max. total current: 

See Power supply (A1-A2)

Impulse withstand voltage (U

imp

): 

0.8 kV

Rated insulation voltage (U

i

):  

32 V

Protected against short circuit: 

yes

Galvanic separation: 

no

9.9 Semiconductor safety output circuits (OSx)

Number of output contacts: 

4

Rated voltage 24V-0V: 

24 Vdc

Output type: 

PNP

Maximum current per output: 

0.5 A

Max. total output current:  

2 A

Minimum current: 

10 mA

Maximum capacitive load to ground per output: 400 nF
Maximum inductive load per output: 

500 mh

Protection fuse: 

2 A type gG

Galvanic separation: 

yes

Impulse withstand voltage (U

imp

): 

0.8 kV

Rated insulation voltage (U

i

): 

32 V

Short circuit detection between outputs:  yes
Duration of the deactivation impulses at the safety outputs: < 300 µs

9.10 Compliance with standards

EN 60204-1, EN ISO 13855, EN ISO 14118, EN ISO 12100, EN ISO 13850, EN 60529, 
EN 61000-6-2, EN 61000-6-3, EN 61326-1, EN 61326-3-1, EN 60664-1, EN 60947-1, 
EN 60947-5-1, EN IEC 63000, EN ISO 13849-1, EN ISO 13849-2, EN 62061, 
EN 62326-1, EN 61131-6, UL 508, CSA C22.2 n° 14-95, GB/T14048.5-2017

9.11 Compliance with directives

Machinery Directive 2006/42/EC, EMC Directive 2014/30/EU, RohS Directive 
2011/65/EU.

 10 SPECIAL VERSIONS ON REQUEST

Special versions of the device are available on request.
These special versions may differ substantially from the indications in these operating 
instructions.
The installer must ensure that he has received written information regarding the use 
of the special version requested (see paragraph SUPPORT).

 11 DISPOSAL

At the end of service life product must be disposed of properly, according to the 
rules in force in the country in which the disposal takes place.

 12 SUPPORT

The device can be used for safeguarding people’s physical safety, therefore in case of 
any doubt concerning installation or operation methods, always contact our technical 
support service:
Pizzato Elettrica Srl
Via Torino, 1 - 36063 Marostica (VI) - ITALY
Tel39.0424.470.930 
E-mail [email protected]
www.pizzato.com
Our support service provides assistance in Italian and English.

Summary of Contents for CS MP310 Series

Page 1: ...l modulo di sicurezza che orientata all applicazione del cliente Power On lo stato del modulo di sicurezza che dura dal momento dell accensione fino alla fine dei controlli interni Run lo stato del mo...

Page 2: ...llo specificato il dispositivo potrebbe non fornire una protezione efficace per l operatore La categoria di sicurezza del sistema secondo EN ISO 13849 1 comprendente il dispositivo di sicurezza dipend...

Page 3: ...nto esterno 3 interno 2 Tensione ad impulso Uimp 0 8 kV Tensione nominale di isolamento Ui 32 V Categoria di sovratensione II Distanze in aria e superficiali secondo EN 60947 1 9 3 Alimentazione A1 A2...

Page 4: ...piego i dettagli su controlli esterni le informazioni sull installazione e il funzionamento sono forniti al meglio delle nostre conoscenze Ad ogni modo ci non significa che dalle caratteristiche descr...

Page 5: ...n this state the module switches to the safe state i e all safety outputs are deactivated Fault a fault can be internal or external to the safety module Internal faults are autonomously detected thank...

Page 6: ...directive requirements The documents necessary for a correct installation and maintenance are always available in the following languages English French German and Italian This device can only be ins...

Page 7: ...12 24 V On Galvanic separation no Minimum duration of input signal 10 ms Input signal filtering yes maximum interference period 0 4 ms Maximum input resistance 100 Maximum input capacitance 470 nF to...

Page 8: ...users are not absolved from the obligation to read and understand our information and recommendations and pertinent technical standards before using the products for their own purposes Taking into acc...

Page 9: ...e celui qui est d crit dans le paragraphe Caract ristiques techniques 4 FONCTIONNEMENT 4 1 D finitions Programme d application partie du logiciel interne du module de s curit qui est orient e vers l a...

Page 10: ...tif en aucun cas Le dispositif sert prot ger les op rateurs Une mauvaise installation ou une mani pulation intempestive peuvent causer de graves blessures voire la mort des dom mages mat riels et des...

Page 11: ...RISTIQUES TECHNIQUES 9 1 Bo tier Mat riau Polyamide PA 66 autoextinguible V0 selon UL 94 Degr de protection IP40 bo tier IP20 bornier Section des c bles 0 2 2 5 mm2 24 12 AWG Couple de serrage des bo...

Page 12: ...us r serve d erreurs et de modifications sans pr avis Les donn es pr sent es dans ce docu ment sont soigneusement contr l es et constituent des valeurs typiques de la production en s rie Les descripti...

Page 13: ...des Ger ts in einem Anwendungsbereich der im Abschnitt Techni sche Daten nicht aufgef hrt ist 4 BETRIEB 4 1 Definitionen Anwendungsprogramm der auf die Anwendung des Kunden ausgerichtete Teil der inte...

Page 14: ...60715 befes tigen Krafteinwirkung durch Biegen oder Drehen vermeiden Das Ger t darf niemals ge ffnet oder modifiziert werden Aufgabe des Ger tes ist der Personenschutz Eine unsachgem e Montage oder M...

Page 15: ...s abh ngt b F lle die in der vorliegenden Anleitung nicht aufgef hrt sind 8 BESCHRIFTUNGEN Das Ger t hat eine extern sichtbar angebrachte Beschriftung Die Beschriftung ent h lt Logo des Herstellers Ar...

Page 16: ...schinenrichtlinie 2006 42 EG ist Die vollst ndige Version der Konformit tserkl rung ist auf der Webseite www pizzato com erh ltlich Marco Pizzato AUSSCHLUSSKLAUSEL Technische nderungen ohne vorherige...

Reviews: