30
19
Integral Time
Integral time. Process
inertia in seconds
0.0-999.9 seconds
(0 integral disabled) Default: 0.
20
Derivative
Time
Derivative time. Normally
¼ the integral time
0.0-999.9 seconds (0 derivative
disabled)
Default: 0.
21
Cycle Time
Cycle time (for PID on
remote control switch
10/15sec, for PID on
SSR 1 sec) or servo
time (value declared by
servo-motor
manufacturer)
1-300 seconds
Default: 10.
22
Output Power
Limit
Limit of output power
10-100 %
Default: 100.
23
Alarm 1
Alarm 1 selection.
Intervention of the alarm
is associated with AL1
(Disabled) Default
(Absolute Alarm)
(Band Alarm)
(High Deviation Alarm)
(Low Deviation Alarm)
(Absolute Command setpoint Alarm)
(Start Alarm) Active in Run
(Cooling)
(Loop Break Alarm)
24
Alarm 1 State
Output
Alarm 1 output contact
and intervention type
(n.o. start) Default
Normally open, active at start
(n.c. start)
Normally closed, active at start
(n.o. threshold)
Normally open, active on reaching
alarm
4
(n.c. threshold)
Normally closed on reaching alarm
44
4
On activation, the output is inhibited if the controller is in alarm mode. Activates only
if alarm condition reappers, after that it was restored.