8.1 Loop Break Alarm on Amperometric Transformer TA
This function allows to measure load current and to manage an alarm
during malfunctioning with power in short circuit or always off. The
amperometric transformer connected to terminals 15 and 16 must be
50mA (sampling time 80ms).
•
Set scale end value of the amperometric transformer in Amperes
on parameter 47
•
Set the intervention threshold of the Loop break alarm in Amperes
on parameter 48
•
Set the intervention delay time of the Loop break alarm on
parameter 49
•
You can associate the alarm with a relay by setting the parameter
,
or
as
.
If a remote control switch or SSR remains closed, the controller signals
the fault by showing
on display 2 (alternatively with a
command setpoint).
If instead the power stage remains open, or the load current is lower
than the value set on
, the controller shows
on
display.
You can display the current absorbed during the closure phase of the
power stage.
Press
Effect
Operation
1
This key enables to scroll
on display 2 the output
percentage, auto/man
selection, setpoint and
alarms
Press
until the writing
appears on
display 1 and display 2
shows the current in
amperes (
>0).
The value is also
maintained when no
current circulates on the
load.