29
corrects the room
temperature value)
10
Gain
Calibration
Gain calibration
Value multiplied with
process value to perform
calibration on working
point
-10.0%…+10.0%
Default: 0.0.
11
Action type
Regulation type
: Heating (N.O.) Default
: Cooling (N.C.)
: HEat Off Over Setpoint
12
Command
Reset
Type of reset for state of
command contact
(always automatic in PID
functioning)
(Automatic Reset) Default
(Manual Reset)
(Manual Reset Stored)
13
Command
State Error
State of contact for
command output in case
of error
Default
14
Command
Led
State of the OUT1 led
corresponding to the
relevant contact
Default
15
Command
Hysteresis
Hysteresis in ON/OFF or
dead band in P.I.D.
-999…+999 digit
∗
(decimi di grado se temperatura)
Default: 0.0.
16
Command
Delay
Command delay (only in
ON/OFF functioning).
(In case of servo valve it
also functions in PID and
represents the delay
between the opening and
closure of the two
contacts)
-180…+180 seconds (tenths of
second in case of servo valve).
Negative: delay in switching off
phase.
Positive: delay in activation phase
Default: 0.
17
Command
Setpoint
Protection
Allows or not to change
the command setpoint
value
Default
18
Proportional
Band
Proportional band
Process inertia in units
(E.g.: if temperature is in
°C)
0 on/off se
Equal to 0. Default
1-9999 digit* (degrees if
temperature)
∗
The display of the decimal point depends on the setting of parameter
and parameter
.