pag. 19
Serial Write
PROFIBUS OUT
The means of the fields are:
In the field “
Slave ID
” the address of the Modbus device that you must write is defined;
In the field “
Type
” insert the data type of the Register you would like to write. You can choose between “Coil Status” and “Holding Register”.
In the field “
Address
” the start address of the register to be written is defined;
In the field “
NPoint
” insert the number of consecutive registers to be written;
In the field “
Poll Time
” insert the cyclic time to make this request;
If the field “
On Change
” is checked, the Modbus writing request is made only if PROFIBUS data are changed; otherwise it is sent cyclically, using the “Poll Time”;
In the field “
Max Error
” the number of consecutive errors that the Master waits before discarding the row from the cycle of requests is defined;
In the field “
Position
” the address for the PROFIBUS array is defined;
The field “
Start Bit
” is used for the “Coil Status” and it allows to select which bit of the selected Position using;
If the field “
SWAP
” is checked, the data written is swapped
In the field “
Mnemonic
” the description for the request is defined.
Figure 7: “Set Modbus Access / Modbus Write --> PROFIBUS Out” window