pag. 21
ASYNC MODBUS REQUEST:
With the Async Modbus Request is possible to send an Asynchronous Modbus Request form the PROFIBUS to the Modbus network.
To use this feature there are 8 bytes in write where the master PROFIBUS can send the parameters of the request and 4 bytes in read where the result of the Modbus
communication is saved.
The parameter in write are:
BYTE
NAME
DESCRIPTION
1
Control_TX
It is the Control byte used to send the request
2
Spare
Not used/ Reserved
3
ID_Device
The ID of the Modbus Slave where to send the request
4
Function_Code
The Function Code of the request
5, 6
Address
Address of the Status/Register to read/write
7, 8
W_Value
Value to write (only if it is a Write request)
The Status in Read are:
BYTE
NAME
DESCRIPTION
1
Control_RX
It is the Control Byte used to send the status of the request modbus
2
Status_Request
It is the result of the Modbus request
3, 4
R_Value
Read value (only if it is a Read request)
The permits values for the “Function Code” are:
•
1
Read one Coil Status
•
2
Read one Input Status
•
3
Read one Holding Register
•
4
Read one Input Register
•
5
Write one Coil Status
•
6
Write one Holding Register
•
15
Write one Coil Status
•
16
Write one Holding Register