Table of Anomaly Signals
If installation malfunctions, controller will switch off regulation output
and will report the anomaly. For example, controller will report failure of a
connected thermocouple visualizing
(fl ashing) fl ashing on display.
For other signals see table below.
Cause
What to do
EEPROM programming error.
Call Assistance.
Cold junction temperature
sensor failure or environment
temperature out of range.
Call Assistance.
Incorrect confi guration data.
Possible loss of instrument
calibration.
Verify that confi guration
parameters are correct.
Sensor connected to AI1 broken
or temperature out of range.
Control connection with probes
and their integrity.
Sensor connected to AI2 broken
or temperature out of range.
Control connection with probes
and their integrity.
Missing calibration.
Call Assistance.
Incorrect control parameters.
Verify control parameters.
Incorrect alarms parameters.
Verify alarm parameters.
Incorrect retransmission
parameters.
Verify retransmission
parameters.
Incorrect visualization
parameters.
Verify visualization parameters.
Incorrect remote setpoint
parameters.
Verify remote setpoint
parameters.