ATR401 - User manual
41
44
Alarm 1 Delay
-600…+600 seconds.
Negative: delay at exit from alarm.
Positive: delay at starting of alarm.
Default
: 0.
45
Alarm 1 Setpoint Protection
Alarm 1 set protection. Does not allow the user to change setpoint
Modifi cation allowed (
Default
)
Protected
Protected and not visualized
46
Alarm
2
Alarm 2 selection. Alarm intervention is associated to AL2
dis. Disabled
(
Default
)
Absolute alarm, referring to process
Band
alarm
Upper deviation alarm
Lower deviation alarm
Absolute alarm, referring to command setpoint
Status alarm (active in Run / Start)
Cooling
action
Load control alarm (Heater Break Alarm)
Sensor failure alarm (Loop Break Alarm)
-Example: status of contactor/ SSR or heating elements
47
Alarm 2 Process
Selects value related to alarm 2
Process 1 (
Default
)
Process
2
Processes
mean
Processes
diff erence
Processes diff erence as absolute value
AI1+AI2 Input addition
48
Alarm 2 State Output
Alarm 2 output contact and type of action
(N.O. start) Normally open, active from Start (
Default
)
(N.C. start) Normally closed, active from Start
Summary of Contents for ATR 401