24
ATR401 - User manual
Integral time
and
derivative time
are the same for both actions.
Parameter
sets the percentage overlapping between the two actions.
For installations where heating and cooling output cannot be activated at the
same time, a dead band will be confi gured (
≤ 0),
vice versa an overlapping will be confi gured (
> 0).
Figure here below shows an example of double action P.I.D. (heating-cooling)
with
= 0 and
= 0.
SPV
PV
ATTIVO
ACTIVE
ATTIVO
ACTIVE
x
(COOL-FREDDO)
< 0
(HEAT-CALDO)
COMMAND OUTPUT (HEAT)
ALARM OUTPUT (COOL)
SPV
PV
ATTIVO
ACTIVE
ATTIVO
ACTIVE
x
(COOL-FREDDO)
= 0
(HEAT-CALDO)
COMMAND OUTPUT (HEAT)
ALARM OUTPUT (COOL)
SPV
PV
ATTIVO
ACTIVE
ATTIVO
ACTIVE
x
(COOL-FREDDO)
> 0
(HEAT-CALDO)
COMMAND OUTPUT (HEAT)
ALARM OUTPUT (COOL)