ATR401 - User manual
47
77
Proportional Band Multiplier
Proportional band for cooling action is given by parameter 30 multiplied
for this parameter
1.00…5.00
Default
: 1.00
78
Overlap / Dead Band
Dead band combination for heating / cooling P.I.D.
-20.0…50.0%.
Negative: Dead band.
Positive: overlap.
Default
: 0.0.
79
Cooling Cycle Time
Cycle Time for Cooling output
1…300 seconds
Default
: 10
80
Conversion
Filter
ADC Filter: Number of sensor readings to calculate mean that defi nes
process value.
NB
: When readings increase, control loop speed slows down
Disabled
2 Samples Mean (Mean with 2 samples)
3 Samples Mean
4 Samples Mean
5 Samples Mean
6 Samples Mean
7 Samples Mean
8 Samples Mean
9 Samples Mean
10 Samples Mean
11 Samples Mean
12 Samples Mean
13 Samples Mean
14 Samples Mean
15 Samples Mean