40
ATR401 - User manual
38
Alarm 1 Process
Select value correlated to alarm 1.
Process 1 (
Default
)
Process
2
Processes
mean
Processes
diff erence
. Processes diff erence as absolute value
AI1+AI2 Input addition
39
Alarm 1 State Output
Alarm 1 output contact and type of action
. (N.O. start) Normally open, active from start (
Default
)
(N.C. start) Normally closed, active from start
(N.O. threshold) Normally open, active from alarm reaching
6
(N.C. threshold) Normally closed, active from alarm reaching
6
40
Alarm 1 Hysteresis
-999…+999 digit
7
(tenths of degree if temperature),
Default
: 0.0.
41
Alarm 1 Rearmament
Type of reset for contact of alarm 1
Automatic Reset (
Default
)
Manual Reset by keyboard
Manual reset stored (keeps relay status also after an eventual
power failure)
42
Alarm 1 State Error
Contact status for alarm 1 output in case of error
Open contact (
Default
)
Closed
contact
43
Alarm 1 Led
Defi nes led A1 status corresponding to relevant contact
ON with open contact
ON with closed contact (
Default
)
6
On activation, the output is inhibited if the controller is in alarm mode. Activates only if alarm
condition reappers, after that it was restored.
7
The display of the decimal point depends on the setting of parameter
. and
or
and