ATR401 - User manual
43
55
Alarm
3
Alarm 3 selection. Alarm intervention is associated to AL3
Disabled
(
Default
)
Absolute alarm, referring to process
Band
alarm
Upper deviation alarm
Lower deviation alarm
Absolute alarm, referring to command setpoint
Status alarm (active in Run / Start)
Cooling
action
Load control alarm (Heater Break Alarm)
Sensor failure alarm (Loop Break Alarm)
Example: status of contactor/ SSR or heating elements
56
Alarm 3 Process
Selects value correlated to alarm 3
Process 1 (
Default
)
Process
2
Processes
mean
Processes
diff erence
Processes diff erence as absolute value
AI1+AI2 Input addition
57
Alarm 3 State Output
Alarm 3 output contact and type of action
(N.O. start) Normally open, active from start (
Default
)
(N.C. start) Normally closed, active from start
(N.O. threshold) Normally open, active from alarm reaching
10
(N.C. threshold) Normally closed, active from alarm reaching
10
58
Alarm 3 Hysteresis
-999…+999 digit
11
(tenths of degree if temperature),
Default
: 0.0.
10
On activation, the output is inhibited if the controller is in alarm mode. Activates only if alarm
condition reappers, after that it was restored.
11
The display of the decimal point depends on the setting of parameter
. and
or
and