ATR401 - User manual
25
Parameter
has the same meaning of cycle time for heating action
Parameter
(Cooling Fluid) pre-selects the proportional band multiplier
and the cooling P.I.D. cycle time
according to cooling fl uid type:
Cooling fl uid type
Air
1.00
10
Oil
1.25
4
Water
2.50
2
Once parameter
, has been selected, the parameters
,
and
can be however modifi ed.
9.2
Heater Break Alarm by current transformer (T.A. input)
This function allows to measure load current and to manage an alarm in case
of malfunctioning (with power in short circuit or always off ).
The current transformer connected to terminals 15 and 16 must be 50 mA
(sampling time 100 ms).
• Set end scale value of the current transformer in Amperes on par. 73
• Set the intervention threshold of the Heater Break Alarm in Amperes on
par. 74
• Set the intervention delay time of the Heater Break Alarm on par. 75
• It is possible to associate the alarm with a relay by setting the parameter
,
,
or
as
If a remote control switch or SSR remains closed, controller signals the fault by
showing
on display 2 (alternatively with a command setpoint).
If the power stage remains open, or the load current is lower than the value
set on
, controller shows
on display. It is possible to display the
current absorbed during the closure phase of the power stage.
Press
Display
Do
1
FNC
This key enables to scroll
on display 2 the output
percentage, auto / man
selection, setpoint and alarms.
Press
FNC
until the writing
appears on display
1 and display 2 shows the
current in amperes (
>0).
The value is also maintained
when no current circulates on
the load.
Setting on parameter 74
the value 0 it is possible to visualize the
current absorbed without generating the Heater Break Alarm.