ATR401 - User manual
29
Modbus
address
Descrizione
Read Write
Reset
value
1017
Start / Stop
0 = Controller in STOP
1 = Controller in START
R/W
0
1018
Lock conversion ON / OFF
0 = Lock conversion off
1 = Lock conversion on
R/W
0
1019
Tuning ON / OFF
0 = Tuning off
1 = Tuning on
R/W
0
1020
Automatic / Manual selection
0 = Automatic
1 = Manual
R/W
0
1021 OFF LINE* time (milliseconds)
R/W
-
1022
Digital input status
0 = Input OFF
1 = Input ON
RO
-
1023 Instantaneous current value (tenth of ampere)
RO
0
1024 Current ON value (tenth of ampere)
RO
0
1025 Current OFF value (tenth of ampere)
RO
0
1100 Process with decimal point selection
RO
-
1101 Setpoint 1 with decimal point selection
R/W
EEPROM
1102 Setpoint 2 with decimal point selection
R/W
EEPROM
1103 Setpoint 3 with decimal point selection
R/W
EEPROM
1104 Setpoint 4 with decimal point selection
R/W
EEPROM
1105 Alarm 1 with decimal point selection
R/W
EEPROM
1106 Alarm 2 with decimal point selection
R/W
EEPROM
1107 Alarm 3 with decimal point selection
R/W
EEPROM
1108 Alarm 4 with decimal point selection
R/W
EEPROM
1109
Real setpoint (gradient) with decimal point
selection
RO
EEPROM
1110 Percentage heating output (0-1000)
R/W
0
*
Se vale 0 il controllo è disabilitato. Se diverso da 0, è “Il tempo massimo che può trascorrere tra
due interrogazioni senza che il regolatore si porti in Off -Line”. In Off -Line il regolatore va in stato
di Stop.