Service life graph

The service life graphs indicate the number of cycles from which failures due to wear must
be expected. The wear is mainly caused by the electrical load; the mechanical load is negli-
gible.

Number of cycles x 1000

Switching current (A)

Example

}

Inductive load: 0.2 A

}

Utilisation category: AC15

}

Contact service life: 4 000 000 cycles

Provided the application to be implemented requires fewer than 4 000 000 cycles, the PFH
value (see Technical details) can be used in the calculation.
To increase the service life, sufficient spark suppression must be provided on all output
contacts. With capacitive loads, any power surges that occur must be noted. With DC con-
tactors, use flywheel diodes for spark suppression.

Order reference

Product type

Features

Connection type

Order no.

PNOZ X7P C

24 VAC/DC

Spring-loaded terminals

787 059

PNOZ X7P

24 VAC/DC

Screw terminals

777 059

PNOZ X7P C

110 - 120 VAC

Spring-loaded terminals

787 053

PNOZ X7P

110 - 120 VAC

Screw terminals

777 053

PNOZ X7P C

230 - 240 VAC

Spring-loaded terminals

787 056

PNOZ X7P

230 - 240 VAC

Screw terminals

777 056

Summary of Contents for PNOZ X7P

Page 1: ...PNOZ X7P Operating Manual 21027 EN 05 Safety relays...

Page 2: ...umentation will be gratefully received Source code from third party manufacturers or open source software has been used for some components The relevant licence information is available on the Interne...

Page 3: ...Disposal 6 For your safety 6 Unit features 7 Safety features 7 Block diagram terminal configuration 7 Types AC 7 Types AC DC 8 Function Description 8 Operating modes 8 Timing diagram 9 Installation 9...

Page 4: ...ly important is identified as follows DANGER This warning must be heeded It warns of a hazardous situation that poses an immediate threat of serious injury and death and indicates preventive measures...

Page 5: ...liant electrical installation The product is designed for use in an industrial environment The product may cause interference if installed in other environments If installed in other environments meas...

Page 6: ...the generic and specialist standards applicable to the spe cific application Warranty and liability All claims to warranty and liability will be rendered invalid if The product was used contrary to th...

Page 7: ...ty relay meets the following safety requirements The circuit is internally redundant with built in self monitoring The safety device remains effective in the case of a component failure The correct op...

Page 8: ...ck loop Y1 Y2 is closed Input circuit is closed e g E STOP pushbutton not operated The LED CH 1 2 lights Safety contacts 13 14 and 23 24 are closed The unit is active Input circuit is opened e g E STO...

Page 9: ...closes before start circuit b Start circuit closes before input circuit t1 Switch on delay t2 Delay on de energisation t3 Recovery time Installation The unit should be installed in a control cabinet w...

Page 10: ...circuit Capacitance is negligible 1 phase Max cable length Imax 1 km Stub circuit Loop circuit Cable length lmax PNOZ X7P AC lmax PNOZ X7P AC WARNING If the max overall line capacitance is exceeded th...

Page 11: ...4 1 are met Preparing for operation Supply voltage AC 24 VAC DC A1 A2 L1 N FE Input circuit Single channel Dual channel E STOP S1 A1 L L1 Safety gate S1 L L1 A1 Start circuit Automatic start Manual st...

Page 12: ...accordance with the European Machinery Directive a check must be carried out to ensure that the safety contacts on the relay outputs open correctly Open the safety contacts switch off output and start...

Page 13: ...respective fault has been rectified and the supply voltage is switched off for approx 1 minute the unit is ready for operation again Contact malfunctions If the contacts have welded reactivation will...

Page 14: ...DC 1 5 W Frequency range AC 50 60 Hz 50 60 Hz 50 60 Hz Residual ripple DC 160 Duty cycle 100 100 100 Max inrush current im pulse Current pulse A1 1 7 A Pulse duration A1 8 ms Inputs 777053 777056 7770...

Page 15: ...gory of safety contacts AC15 at 230 V 230 V 230 V Max current 4 A 4 A 5 A DC13 6 cycles min at 24 V 24 V 24 V Max current 4 A 4 A 6 A Utilisation category in ac cordance with UL Voltage 240 V AC G P 2...

Page 16: ...th E STOP typ 70 ms 70 ms 45 ms With E STOP max 100 ms 100 ms 70 ms With power failure typ 70 ms 70 ms 45 ms With power failure max 100 ms 100 ms 70 ms Recovery time at max switching frequency 1 s Aft...

Page 17: ...es 10 000 000 cycles 10 000 000 cycles Material Bottom PPO UL 94 V0 PPO UL 94 V0 PPO UL 94 V0 Front ABS UL 94 V0 ABS UL 94 V0 ABS UL 94 V0 Top PPO UL 94 V0 PPO UL 94 V0 PPO UL 94 V0 Connection type Sc...

Page 18: ...r supply DC 1 5 W Frequency range AC 50 60 Hz 50 60 Hz 50 60 Hz Residual ripple DC 160 Duty cycle 100 100 100 Max inrush current im pulse Current pulse A1 1 7 A Pulse duration A1 8 ms Inputs 787053 78...

Page 19: ...gory of safety contacts AC15 at 230 V 230 V 230 V Max current 4 A 4 A 5 A DC13 6 cycles min at 24 V 24 V 24 V Max current 4 A 4 A 6 A Utilisation category in ac cordance with UL Voltage 240 V AC G P 2...

Page 20: ...th E STOP typ 70 ms 70 ms 45 ms With E STOP max 100 ms 100 ms 70 ms With power failure typ 70 ms 70 ms 45 ms With power failure max 100 ms 100 ms 70 ms Recovery time at max switching frequency 1 s Aft...

Page 21: ...unting position Any Any Any Mechanical life 10 000 000 cycles 10 000 000 cycles 10 000 000 cycles Material Bottom PPO UL 94 V0 PPO UL 94 V0 PPO UL 94 V0 Front ABS UL 94 V0 ABS UL 94 V0 ABS UL 94 V0 To...

Page 22: ...fety function s SIL PL values are not identical to the SIL PL values of the units that are used and may be different We recommend that you use the PAScal software tool to calculate the safety function...

Page 23: ...000 cycles the PFH value see Technical details can be used in the calculation To increase the service life sufficient spark suppression must be provided on all output contacts With capacitive loads a...

Page 24: ...eet the requirements of the directive 2006 42 EC for ma chinery of the European Parliament and of the Council The complete EC Declaration of Conformity is available on the Internet at www pilz com sup...

Page 25: ...fetyNET p THE SPIRIT OF SAFETY are registered and protected trademarks of Pilz GmbH Co KG in some countries We would point out that product features may vary from the details stated in this document d...

Reviews: